Configuration data

Index 8000 COM Settings

Index (hex)

Name

Meaning

Data type

Flags

Default

8000:0

COM Settings

Maximum subindex

UINT8

RO

>27<

8000:11

Baud rate

Baud rate
1: 300 Baud
2: 600 Baud
3:1200 Baud
4: 2400 Baud
5: 4800 Baud
6: 9600 Baud
7: 19.2 kbaud
8: 38.4 kbaud
9: 57.6 kbaud
10: 115.2 kbaud
11: Use explicit baudrate (subindex 0x1B)
12: 76.8 kbaud

BIT4

RW

9600 Baud (6)

8000:1A

Rx buffer full notification

The value specifies the number of data in the receive FIFO, from which the bit “buffer full” is set.

UINT16

RW

0x0360 (864dec)

8000:1B

Explicit baudrate

In this object the desired baud rate can be entered directly as a number.

(can be activated in object 8000:11)

UINT32

RW

0x00002580 (9600dec)

Index 800F COM Ext Settings

Index (hex)

Name

Meaning

Data type

Flags

Default

800F:0

COM Ext Settings

Maximum subindex

UINT8

RO

>1<

800F:01

Tx buffer Low Water

([800F:01] & 0x0FFF

If the number of bytes still to be sent is smaller than ([800F:01] & 0x0FFF ), the Tx Buffer Empty flag (0x6001:08) is set

UINT16

RW

0x0000 (0dec)

Bit 12

1: The explicitly set baud rate is not checked for min (300) and max (256,000)

Bit 13

1: Invalid input data is zeroed

Bit 14

res.

Bit 15

0: 8 byte blocks are copied into each process data input

1: 128 byte blocks are copied into each process data input