Output data (0x7xxx)

Index 7000 Control

Index (hex)

Name

Meaning

Data type

Flags

Default

7000:0

Control

Maximum subindex

UINT8

RO

>19<

7000:01

Ctrl_Toggle Send

Toggles when sending

BOOLEAN

RW

FALSE

7000:02

Ctrl_Frame Type

Frame type

0: "16 Bit"
1: "24 Bit"
2: "32 Bit"

BIT3

RO

0x00 (0dec)

7000:05

Ctrl_Priority

Priority

0: "High"
1: "Middle High"
2: "Middle"
3: "Middle Low"
4: "Low"

BIT3

RO

0x00 (0dec)

7000:08

Ctrl_Send Twice

Send DALI command twice (send twice*)

BOOLEAN

RW

FALSE

7000:09

Ctrl_Clear RxBuffer

Clear command buffer

BOOLEAN

RW

FALSE

7000:0A

Ctrl_Get RxBuffer Entry

Toggle to read the next buffer entry (see 0x6000:06).

BOOLEAN

RW

FALSE

7000:0B

Ctrl_Release blocking of PLC Commands

Release blocking of PLC commands

BOOLEAN

RW

FALSE

7000:0C

Ctrl_Start Addressing

Start addressing

BOOLEAN

RW

FALSE

7000:0D

Ctrl Addressing Options

Addressing options

BIT2

RO

0x00 (0dec)

7000:11

Addressing Start Address

Addressing Start address

UINT8

RO

0x00 (0dec)

7000:13

Frame

Frame

UINT32

RO

0x00000000 (0dec)

*) Certain DALI commands must be sent twice within 100 ms (send twice) without the receiver receiving any other DALI commands in the meantime (primarily commands for configuring DALI devices)