Configuration data (0x8xxx)

Index 8000 Emergency Message

Index (hex)

Name

Meaning

Data type

Flags

Default

8000:0

Emergency Message

Maximum subindex

UINT8

RO

>14<

8000:01

Frame Type

Frame type:

0: "No Frame" (factory setting)
1: "16 Bit"
2: "24 Bit"
3: "32 Bit"

BIT2

RW

0x00 (0dec)

8000:03

Frame Priority

Frame priority

0: "High" (factory setting)
1: "Middle High"
2: "Middle"
3: "Middle Low"
4: "Low"

BIT3

RW

0x00 (0dec)

8000:06

Block PLC Options

0: "Do Nothing" (factory setting)

1: "Block PLC Options"
PLC-controlled DALI commands are ignored

BIT2

RW

0x00 (0dec)

8000:0E

Frame

The received DALI telegram (raw data)

UINT32

RW

0x00000000 (0dec)

Index 8001 Settings

Index (hex)

Name

Meaning

Data type

Flags

Default

8001:0

Settings

Maximum subindex

UINT8

RO

>1<

8001:01

Ignore non affecting Collisions

TRUE (factory setting):
Non affecting collisions are ignored

FALSE:
Non affecting collisions are not ignored

BOOLEAN

RW

0x00 (0dec)

8001:02

Ignore 16 Bit Frames

TRUE (factory setting):
16-bit frames are ignored

FALSE:
16-bit frames are not ignored

BOOLEAN

RW

0x00 (0dec)

8001:03

Ignore 24 Bit Frames

0: "Off" (factory setting)
24-bit frames are not ignored

1: "Ignore all but Events"
Everything is ignored except events

2: "Ignore all"
Everything is ignored

BIT3

RW

0x00 (0dec)

8001:05

Ignore 32 Bit Frames

TRUE:
32-bit frames are ignored

FALSE (factory setting):
32 bit frames are not ignored

BOOLEAN

RW

0x00 (0dec)

8001:08

Enable Power Supply

Enable power supply

TRUE (factory setting): Power supply is switched on

FALSE: Power supply is switched off

BOOLEAN

RW

0x01 (1dec)

8001:09

DALI Short Address

DALI short address

UINT8

RW

0xFF (255dec)

Index 8002 Memory Bank 2

Index (hex)

Name

Meaning

Data type

Flags

Default

8002:0

Memory Bank 2

Maximum subindex

UINT8

RO

>1<

8002:01

Offset of last memory area

Offset of the last memory area inside the memory bank that can be accessed.

UINT8

RO

0xFE (254dec)

8002:02

Indicator Byte

Indicator Byte

UINT8

RO

0x00 (0dec)

8002:03

Lock Byte

Lock byte for the memory bank

UINT8

RO

0xFF (255dec)

8002:04

Additional Device Information #03

Additional device information

UINT8

RW

0x00 (0dec)

…

…

…

UINT8

RW

0x00 (0dec)

8002:FF

Additional Device Information #254

Additional device information

UINT8

RW

0x00 (0dec)

Index 8010 Input Settings Ch. 1

Index (hex)

Name

Meaning

Data type

Flags

Default

8010:0

Input Settings Ch. 1

Maximum subindex

UINT8

RO

>1<

8010:01

Frame Type falling Edge

Frame type on falling edge at "Input 1"

0: "No Frame" (factory setting)
1: "16 Bit"
2: "24 Bit"
3: "32 Bit"

BIT3

RW

0x00 (0dec)

8010:03

Frame Priority falling Edge

Frame priority on falling edge at "Input 1"

0: "High" (factory setting)
1: "Middle High"
2: "Middle"
3: "Middle Low"
4: "Low"

BIT3

RW

0x00 (0dec)

8010:06

Block PLC Options falling Edge

0: "Do Nothing" (factory setting)

1: "Block PLC Options"
Priority of the digital input "Input 1", PLC-controlled DALI commands are blocked on a falling edge at "Input 1".

2: "Release"
The process image is released again on a falling edge at "Input 1".

BIT3

RW

0x00 (0dec)

8010:08

Frame Type rising Edge

Frame type on rising edge at "Input 1"

0: "No Frame" (factory setting)
1: "16 Bit"
2: "24 Bit"
3: "32 Bit"

BIT3

RW

0x00 (0dec)

8010:0A

Frame Priority rising Edge

Frame priority on rising edge at "Input 1"

0: "High" (factory setting)
1: "Middle High"
2: "Middle"
3: "Middle Low"
4: "Low"

BIT3

RW

0x00 (0dec)

8010:0D

Block PLC Options rising Edge

0: "Do Nothing"

1: "Block PLC Options" (factory setting)
Priority setting of the digital input "Input 1", PLC-controlled DALI commands are blocked on a rising edge at "Input 1".

2: "Release"
The process image is released again on a rising edge at "Input 1".

BIT3

RW

0x01 (1dec)

8010:11

Frame falling Edge

Frame on falling edge at "Input 1"

UINT32

RW

0x00000000 (0dec)

8010:12

Frame rising Edge

Frame on rising edge at "Input 1"

UINT32

RW

0x0000FF05 (65285dec)

Index 8020 Input Settings Ch. 2

Index (hex)

Name

Meaning

Data type

Flags

Default

8020:0

Input Settings Ch. 2

Maximum subindex

UINT8

RO

>18<

8020:01

Frame Type falling Edge

Frame type on falling edge at "Input 2"

0: "No Frame" (factory setting)
1: "16 Bit"
2: "24 Bit"
3: "32 Bit"

BIT3

RW

0x00 (0dec)

8020:03

Frame Priority falling Edge

Frame priority on falling edge at "Input 2"

0: "High" (factory setting)
1: "Middle High"
2: "Middle"
3: "Middle Low"
4: "Low"

BIT3

RW

0x00 (0dec)

8020:06

Block PLC Options falling Edge

0: "Do Nothing" (factory setting)

1: "Block PLC Options"
Priority of the digital input "Input 2", PLC-controlled DALI commands are blocked on a falling edge at "Input 2".

2: "Release"
The process image is released again on a falling edge at "Input 2".

BIT3

RW

0x00 (0dec)

8020:08

Frame Type rising Edge

Frame type on rising edge at "Input 2"

0: "No Frame" (factory setting)
1: "16 Bit"
2: "24 Bit"
3: "32 Bit"

BIT3

RW

0x00 (0dec)

8020:0A

Frame Priority rising Edge

Frame priority on rising edge at "Input 2"

0: "High" (factory setting)
1: "Middle High"
2: "Middle"
3: "Middle Low"
4: "Low"

BIT3

RW

0x00 (0dec)

8020:0D

Block PLC Options rising Edge

0: "Do Nothing"

1: "Block PLC Options" (factory setting)
Priority setting of the digital input "Input 2", PLC-controlled DALI commands are blocked on a rising edge at "Input 2".

2: "Release"
The process image is released again on a rising edge at "Input 2".

BIT3

RW

0x01 (1dec)

8020:11

Frame falling Edge

Frame on falling edge at "Input 2"

UINT32

RW

0x00000000 (0dec)

8020:12

Frame rising Edge

Frame on rising edge at "Input 2"

UINT32

RW

0x0000FF05 (0dec)