Star Hub (Multiport Tap)
Shorter drop line lengths must be maintained when passive distributors ("multiport taps"), such as the Beckhoff ZS5052-4500 Distributor Box. The following table indicates the maximum drop line lengths and the maximum length of the trunk line (without the drop lines):
![]() | Guide values The following values are recommended by BECKHOFF. |
|
Baud rate |
Drop line length with multiport topology |
Trunk line length (without drop lines) |
|---|---|---|
|
500 kbit/s |
< 1.2 m |
< 66 m |
|
250 kbit/s |
< 2.4 m |
< 120 m |
|
125 kbit/s |
< 4.8 m |
< 310 m |