EL6752/-0010 diagnostics

The EL6752/-0010 feature various diagnostic variables that describe the state of the terminal and the DeviceNet® and can be linked in the PLC:

EL6752/-0010 diagnostics 1:

We recommend monitoring the following process data during each cycle:

    • WcState: if ≠ 0, this EtherCAT device does not take part in the process data traffic
    • State: if ≠ 8, the EtherCAT device is not in OP (operational) status
    EL6752/-0010 diagnostics 2:

    We recommend monitoring the following process data:

      • Error: if ≠ 0, the indicated number of DeviceNet® devices has a BoxState not equal zero, i.e. check which DeviceNet® devices are not operating correctly in the bus
      • DiagFlag: indicates pending diagnostic data