Star Hub (Multiport Tap)
Shorter drop line lengths must be maintained when passive distributors ("multiport taps"), such as the Beckhoff ZS5052-4500 Distributor Box. The following table indicates the maximum drop line lengths and the maximum length of the trunk line (without the drop lines):
Baud rate |
Drop line length with multiport topology |
Trunk line length (without drop lines) |
---|---|---|
1 Mbit/s |
< 0,3 m |
< 25 m |
500 kbit/s |
< 1,2 m |
< 66 m |
250 kbit/s |
< 2,4 m |
< 120 m |
125 kbit/s |
< 4,8 m |
< 310 m |