EL6751 – LED description
Fig.4: LEDsLED behavior
The most important states of the terminal can be quickly diagnosed on the basis of the LEDs:
|
LED |
Color |
Meaning | |
|---|---|---|---|
|
RUN |
green |
This LED indicates the terminal's operating state: | |
|
off |
State of the EtherCAT State Machine: | ||
|
Flashes at 2 Hz |
State of the EtherCAT State Machine: | ||
|
Flashes at 1 Hz |
State of the EtherCAT State Machine: | ||
|
on |
State of the EtherCAT State Machine: OP = normal operating state; mailbox and process data communication is possible | ||
|
Err |
red |
off |
All configured bus devices are error-free (box state = 0); TwinCAT task or process is running. |
|
Flashes at 1 Hz |
At least one box state is not equal to 0 (e.g. device not found, wrong configuration, device in error state) | ||
|
Flashes at 10 Hz |
Configuration upload being carried out | ||
|
on |
CAN controller is BUS OFF. Physical CAN problem. Possible causes: e.g. missing termination resistor, bus line too long, wrong baud rate, node address assigned twice, wiring error, short-circuit. | ||
|
CPU error |
red |
on |
EL6751 processor error |
|
Flashes at 10 Hz |
The EL6751 processor starts | ||