Technical data
Technical data | EL6751-0000 | EL6751-0010 |
|---|---|---|
Bus system | CANopen | |
Version | Master | Slave |
Number of fieldbus channels | 1 | |
Data transfer rate | 10, 20, 50, 100, 125, 250, 500, 800 or 1000 kbit/s | |
Bus interface | D-Sub 9-pole connector according to CANopen specification, galvanically uncoupled | |
Bus devices**) | maximum 127 slaves | |
Communication | CANopen network master and CANopen manager | CANopen slave |
Diagnostics | Status LEDs | |
Power supply | via the E-bus | |
Current consumption via E-bus | typ. 230 mA | |
Electrical isolation | 500 V (E-bus/CANopen) | |
Configuration | with TwinCAT System Manager | |
Weight | approx. 70 g | |
Permissible ambient temperature range during operation | -25 °C ... +60 °C (extended temperature range) | |
Permissible ambient temperature range during storage | -40 °C ... +85 °C | |
Permissible relative humidity | 95 %, no condensation | |
Dimensions (W x H x D) | approx. 26 mm x 100 mm x 52 mm (width aligned: 23 mm) | |
on 35 mm mounting rail conforms to EN 60715 | ||
Vibration / shock resistance | conforms to EN 60068-2-6 / EN 60068-2-27 | |
EMC immunity / emission | conforms to EN 61000-6-2 / EN 61000-6-4 | |
Protection class | IP20 | |
Installation position | variable | |
Approvals / markings*) | ||
*) Real applicable approvals/markings see type plate on the side (product marking).
![]() | **) Maximum number of bus devices This value specifies the maximum number of node IDs that can be used. However, this does not mean that 127 nodes can be operated on one CANopen master. |
Ex markings
Standard | Marking |
|---|---|
ATEX | II 3 G Ex nA IIC T4 Gc |
IECEx | Ex nA IIC T4 Gc |