LEDs and connection

LEDs

LEDs and connection 1:
LEDs

LED

Colours

Meaning

RUN 1

green

These LEDs indicate the terminal's operating state:

off

State of the EtherCAT State Machine: INIT = initialization of the terminal

flashing uniformly

State of the EtherCAT State Machine: PREOP = function for mailbox communication and different standard-settings set

flashing slowly

State of the EtherCAT State Machine: SAFEOP = verification of the Sync Manager channels

on

State of the EtherCAT State Machine: OP = normal operating state; mailbox and process data communication is possible

flashing rapidly

State of the EtherCAT State Machine: BOOTSTRAP = function for terminal firmware updates

RC/RD

red

RD signal: outgoing Interbus switched off - if not: outgoing Interbus switched on

RC/RD

green

RC signal: incoming Interbus connected - if not: incoming Interbus not connected

RC/RD

orange

RD signal (red) and RC signal (green) at the same time

BA/CPU error

red

CPU signal error

BA/CPU error

green

BA signal: Interbus ASIC bus active

Pin assignment D sub9 socket/plug connector (plan view)

LEDs and connection 2:

Pin assignment before hardware version 01

Pins 4 and 8 were not assigned before hardware version 01!
The lower diagram shows the pin assignment from hardware version 01.
VCC / GND: E-bus supply voltage
VCC_ISO / GND_ISO: Electrically isolated auxiliary voltage (max. load 60 mA)

LEDs and connection 3:
Connection

Fieldbus signal input

Pin

1

2

3

4

5

6

7

8

9

Signal

DO

DI

GND_ISO

GND

VCC_ISO

/DO

/DI

VCC

NC

Fieldbus signal output

Pin

1

2

3

4

5

6

7

8

9

Signal

DO

DI

GND

GND

VCC

/DO

/DI

VCC

RBST