Technical data

Technical data

EL6740-0010

Fieldbus

Interbus

Function

Slave

Number of fieldbus channels

1

Data transfer rates

2 Mbit (default) / 500 kbaud

Bus interface

2 x D sub plug, 9-pin, plug and socket with screening and vibration lock

Max. number of bytes, fieldbus

32 Word input and 32 Word output

Hardware diagnostics

Status LEDs

Supply voltage for electronics

via the E-bus

Current consumption via E-bus

typ. 450 mA

Electrical isolation

500 V (E-bus/field voltage)

Configuration

via TwinCAT System Manager

Weight

approx. 80 g

Permissible ambient temperature range during operation

0 °C ... + 55 °C
(aligned in standard installation position)
0 °C ... + 45 °C
(all other installation positions, see notice)

Permissible ambient temperature range during storage

-25 °C ... + 85 °C

Permissible relative humidity

95 %, no condensation

Dimensions (W x H x D)

approx. 26 mm x 100 mm x 52 mm (width aligned: 23 mm)

Mounting

on 35 mm mounting rail conforms to EN 60715

Vibration / shock resistance

conforms to EN 60068-2-6 / EN 60068-2-27

EMC immunity / emission

conforms to EN 61000-6-2 / EN 61000-6-4

Protection class

IP20

Installation position

see notice

Approvals / markings*

CE, cULus, UKCA, EAC, ATEX, IECEx

*) Real applicable approvals/markings see type plate on the side (product marking).

Ex markings

Standard

Marking

ATEX

II 3 G Ex nA IIC T4 Gc

IECEx

Ex nA IIC T4 Gc