Profile-specific CoE objects

Profile-specific CoE objects 1:

Reading of CoE objects 0x6000 and 0x7000

The data that are output during reading of CoE objects 0x6000 and 0x7000 are not the real process data. The actual data can only be read indirectly via PDO allocation.

Index (hex)

Name

Meaning

Data type

Flags

Default value

6000:0

Input Data

Declared input process data (dynamically created)

UINT8

RO

0x00 (0dec)

6000:01

6000:FF

Index (hex)

Name

Meaning

Data type

Flags

Default value

7000:0

Output Data

Declared output process data (dynamically created)

UINT8

RO

0x00 (0dec)

7000:01

7000:FF

Index (hex)

Name

Meaning

Data type

Flags

Default value

F000:0

Modular device profile

General information for the modular device profile

UINT8

RO

0x02 (2dec)

F000:01

Module Index (hex) distance

Index (hex) interval of the objects of the individual channels

UINT16

RO

0x0010 (16dec)

F000:02

Maximum number of modules

Number of channels

UINT16

RO

0x0001 (1dec)

Index (hex)

Name

Meaning

Data type

Flags

Default value

F008:0

Code word

currently reserved

UINT32

RW

0x00000000 (0dec)

Index (hex)

Name

Meaning

Data type

Flags

Default value

F010:0

Module list

Max. subIndex (hex)

UINT8

RW

0x01 (1dec)

F010:01

SubIndex (hex) 001

-

UINT32

RW

0x00000000 (0dec)

Currently 64 PDOs, 2 bit per Tx-PDO

bit 0 → 1=mapping present (p)

bit 1 → 1=mapping active (a)

Index (hex)

Name

F630

Active TxPdo

Mapping:

a

p

a

p

a

p

a

p

a

p

a

p

a

p

a

p

0

0

1

1A07

1A06

1A05

1A04

1A03

1A02

1A01

1A00

2

1A0F

1A0E

1A0D

1A0C

1A0B

1A0A

1A09

1A08

3

1A17

1A16

1A15

1A14

1A13

1A12

1A11

1A10

4

1A1F

1A1E

1A1D

1A1C

1A1B

1A1A

1A19

1A18

..

..

..

..

..

..

..

..

8

1A3F

1A3E

1A3D

1A3C

1A3B

1A3A

1A39

1A38

Index (hex)

Bit

Name

Meaning

Comment

F800:0

-

Device Config

 

 

F800:01

0x8000

AoE

1 = protocol disabled

 

 

0x4000

EoE

 

0x2000

FoE

 

0x1000

SoE

 

0x0800

VoE

 

0x0400

other

 

0x0200

-

 

If 0, the system checks whether the MBX protocol ECAT-EEPROM is present

 

 

 

 

 

0x0002

-

 

Suppress error message

 

0x0001

-

 

1: If not routed: error message suppressed

 

 

 

 

0xF800:02

0x0100

FoE Buffer

Enable

 

 

0x2000

Watchdog mode

 

The Watchdog of the EL6695 will be triggered via the AL event "Watchdog" as standard. By a single set of 0x2000 the WriteCycleCounter is used as trigger instead. This setting may be necessary when running under some EtherCAT masters.

 

0x0002

OP State

Deactivate dependence on other side

Deactivate dependence of the operating state on the secondary side (only device emulation)

 

0x0001

OP State

Deactivate dependence of the operating state on the primary side (only device emulation)

0xF800:03

0x2000

 

SW Restart

Reboot during state change from Any to Init (A → I)

 

 

 

 

Index (hex)

Name

Meaning

Data type

Flags

Default value

F820:0

ADS Server Settings

Destination Net ID / Port

Object

RW

0x02 (2dec)

F820:01

Net ID

Destination Net ID

Array [0..5]

RW

0x00, ..

F820:02

Port

Destination Port

UINT16

RW

0x0000

Index (hex)

Name

Meaning

Data type

Flags

Default value

F821:0

EL6695 ADS Settings

Source Net ID / Port

Object

RO

0x02 (2dec)

F821:01

Net ID

Source Net ID

Array [0..5]

RO

0x00, ..

F821:02

Port

Source Port

UINT16

RO

0x0000

Index (hex)

Name

Meaning

Data type

Flags

Default value

FA20:0

Device Diag

Contains diagnostic information on status, CPU and heap load, information on sent data packets and internal copy time

UINT16

RD

0x1D (29dec)

FA20:01

Status

 

UINT16

RD

 

FA20:02

CPU usage [%]

 

UINT16

RD

 

FA20:03

Heap Usage [%]

 

UINT16

RD

 

FA20:04

AOE Packets

 

UINT16

RD

 

FA20:05

EOE Packets

 

UINT16

RD

 

FA20:06

FOE Packets

 

UINT16

RD

 

FA20:07

SOE Packets

 

UINT16

RD

 

FA20:08

VOE Packets

 

UINT16

RD

 

FA20:09

Other Packets

 

UINT16

RD

 

FA20:0A

Mbx Info

 

UINT16

RD

 

FA20:0B

PD Copy time (my)

Time in µs

UINT16

RD

 

FA20:0C

PD Copy time (remote)

UINT16

RD

 

FA20:0D..

Info 2

 

UINT16

RD

 

FA20:1D

Info 18

 

UINT16

RD