Operating conditions for installation
Please ensure that the EL6695 EtherCAT Terminal is only transported, stored and operated under the specified conditions (see technical data)!
| |
Invalid operating conditions must be avoided! The EL6695 must not be used under the following operating conditions: ● under the influence of ionizing radiation ● in corrosive environments ● in an environment that leads to unacceptable soiling of the Bus Terminal |
Safety instructions for installation
Before installing and commissioning the EtherCAT Terminals please read the safety instructions in the foreword of this documentation.
Transport / storage
When transporting or storing the EtherCAT Terminals, always use the original packaging in which they were delivered.
Electrical installation
Please note that the EL6695 preferentially uses the 24 V supply, if both E-bus and 24 V are available. In order to ensure that the EL6695 is supplied via the E-bus, it is therefore advisable commission it with the 24 V supply disconnected. Otherwise, overload may occur in the E-bus supply in the terminal strand in the event of a failure of the 24 V supply, if the E-bus supply was not pre-dimensioned correctly.