Requirement 2a: higher-level global time, absolute time

If the time base TDC is to be adjusted based on a higher-level time base, the time base and the associated procedure must be selected. Generally common synchronization protocols are used for the synchronization. Samples for time sources and synchronization procedures are listed below.

The following synchronization precisions can be achieved (depending on the hardware)

The following two control aims must be achieved:

Requirement 2a: higher-level global time, absolute time 1:

External EtherCAT synchronization

External synchronization sources (e.g. EL6688, EL6692) can only be used from TwinCAT 2.11 used. In older versions of TwinCAT such EtherCAT slaves have no meaningful function.

If a higher-level master clock is integrated in an EtherCAT system, a special EtherCAT device is generally used for the physical connection. The device monitors both time bases and is therefore able to determine the time difference.

Please refer to www.beckhoff.de for suitable products currently available for this purpose.

Requirement 2a: higher-level global time, absolute time 2:Fig.14: EtherCAT topology with external reference clock

The different time bases can be arranged hierarchically, so that at the start of the respective system the current absolute time is taken from the subordinate system. If necessary top-down synchronization is used, if external time bases or DC components are present in the system.

Readjustment of local time vs. higher-level absolute time

For the purpose of synchronization the local DC time is not adjusted based on the higher-level absolute time, but only to a constant offset. This offset is made available to the user as a process data. The offset is corrected by ±½ cycle time to ensure both tasks run in phase.