EL6652-0010 - LEDs
Fig.142: EL6652 LEDsLEDs for EtherCAT diagnosis
|
LED |
Display |
Description | |
|---|---|---|---|
|
RUN |
green |
off |
State of the EtherCAT state machine: |
|
flashes (200 ms) |
State of the EtherCAT state machine: | ||
|
off (1 s) |
State of the EtherCAT state machine: | ||
|
on |
State of the EtherCAT state machine: OP = normal operating state; mailbox and process data communication is possible | ||
LED EIP State
|
Color green |
Color red |
Meaning |
|---|---|---|
|
off |
off |
no EtherNet/IP slave configuration on the EL6652-0010 |
|
on |
off |
All configured IO assemblies are in data exchange with the EtherNet/IP master. All connections are in the run state (cyclic exchange of valid process data) |
|
off (1 s) |
off |
EtherNet/IP slave and IO assembly are correctly parameterized |
|
flashes (400 ms) |
off |
One of the EtherNet/IP slaves has no valid IO assembly configuration |
|
off |
off (1 s) |
A general error occurred with the EtherNet/IP slave |
|
off |
on |
Internal error. Replace the EtherCAT Terminal |
LED NET State
|
Color green |
Color red |
Meaning |
|---|---|---|
|
off |
off |
No link detected |
|
on |
off |
EL terminal has detected a link and was configured correctly |
|
flashes (400 ms) |
off |
At least one Ethernet port has an active link and a configured EtherNet/IP Slave interface has no valid IP address configured |
|
off (1 s) |
off |
All configured EtherNet/I slaves have a valid IP address configuration. UDP and TCP Layer was initialized |
|
off |
on |
Internal error. Replace the EtherCAT Terminal |
|
off |
off (1 s) |
A general error occurred with the EtherNet/IP slave |
LEDs starting up
|
Run |
EIP State |
NET State |
Meaning |
|---|---|---|---|
|
off |
off |
off |
No electrical voltage connected to E-bus. The EL6652-0010 must be exchanged if EtherCAT Terminals behind it need to function. |
|
off |
off |
red on |
EL terminal is starting up; after approx. 10 seconds, the LED should go out. If this does not happen, the EL6652-0010 module must be exchanged. |
|
on |
on |
red on |
EL terminal starts up; the terminal should be ready after approx. 2 - 3 s; the startup is completed as soon as the red "NET State" LED goes out. |