EL6633 – Technical data

Technical data

EL6633

Technology

PROFINET RT

Number of ports/channels

2 (switched)

Fieldbus

PROFINET RT Controller and/or Device

Max. process data size

1.4 kB input/1.4 kB output data

Ethernet interface

10/100/1000BASE-TX Ethernet with 2 x RJ45

Cable length

up to 100 m twisted pair

Hardware diagnostics

Status LEDs

Power supply

via the E-bus

Electrical isolation

500 V (E-bus/Ethernet)

Protocol

RT

Configuration

via the EtherCAT master

Current consumption via E-bus

400 mA typ.

Special features

Conformity class B, supported service protocols RPC and RSI

Maximum number of process data

1 kB input data and 1 kB output data

Maximum number of submodules per PROFINET device

238

Configuration

via the EtherCAT master,
TwinCAT 3 4024.67 or 4026.16 or higher

Installation

on 35 mm mounting rail, conforms to EN 60715

Weight

approx. 75 g

Permissible ambient temperature during operation**)

0…+55 °C

Permissible ambient temperature during storage

-25…+85 °C

Permissible relative humidity

95% no condensation

Vibration / shock resistance

conforms to EN 60068-2-6 / EN 60068-2-27

EMC immunity / emission

conforms to EN 61000-6-2 / EN 61000-6-4

Installation position

Standard installation position (an operating temperature of 45 ℃ applies to other installation positions), see also notice

Protection rating

IP20

Approvals/markings*)

CE, cULus

*) Real applicable approvals/markings see type plate on the side (product marking).