EL6631-0010 - LEDs

LEDs for EtherCAT diagnosis
|
LED |
Display |
Description | |
|---|---|---|---|
|
RUN |
green |
off |
State of the EtherCAT State Machine: |
|
flashing |
State of the EtherCAT State Machine: | ||
|
off (1 s) |
State of the EtherCAT State Machine: | ||
|
on |
State of the EtherCAT State Machine: | ||
LED diagnosis PROFINET RUN/Err
|
Colors green |
Colors red |
Meaning |
|---|---|---|
|
on |
off |
EL terminal is parameterized |
|
off (1 s) |
off |
EL6631-0010 does not have an IP address |
|
flashing |
off |
EL6631-0010 still has not received a PROFINET name |
|
off |
flashing |
Terminal starts |
LED diagnosis PROFINET Err
|
Colors green |
Colors red |
Meaning |
|---|---|---|
|
on |
off |
EL terminal is exchanging data |
|
flashing |
off |
EL terminal is exchanging data, but the provider status is stopped |
|
off (1 s) |
off |
EL terminal is exchanging data, but the modules are different |
|
off |
flashing |
No AR established, |
|
flashing |
flashing |
Identify EL terminal through PROFINET "flashing" |
LEDs starting up
|
Run |
PN Run/Err |
PN Err |
Meaning |
|---|---|---|---|
|
off |
off |
off |
No electrical voltage connected to E-bus. The EL6631-0010 must be exchanged if EtherCAT terminals behind it need to function. |
|
off |
off |
red on |
EL terminal is starting up; after approx. 10 seconds, the LED should go out. If this does not happen, the EL6631-0010 module must be exchanged. |