EL6631-0010 - LEDs

EL6631-0010 - LEDs 1:
Tc_EL6631_LEDs

LEDs for EtherCAT diagnosis

LED

Display

Description

RUN

green

off

State of the EtherCAT State Machine:
INIT
= initialization of the terminal;
BOOTSTRAP = function for terminal firmware updates

flashing
200 ms

State of the EtherCAT State Machine:
PREOP
= function for mailbox communication and different standard-settings set

off (1 s)
on (200 ms)

State of the EtherCAT State Machine:
SAFEOP
= verification of the sync manager channels and the distributed clocks.
Outputs remain in safe state

on

State of the EtherCAT State Machine:
OP = normal operating state; mailbox and process data communication is possible

LED diagnosis PROFINET RUN/Err

Colors green

Colors red

Meaning

on

off

EL terminal is parameterized

off (1 s)
on (200 ms)

off

EL6631-0010 does not have an IP address

flashing
200 ms

off

EL6631-0010 still has not received a PROFINET name

off

flashing
200 ms

Terminal starts

LED diagnosis PROFINET Err

Colors green

Colors red

Meaning

on

off

EL terminal is exchanging data

flashing
200 ms

off

EL terminal is exchanging data, but the provider status is stopped

off (1 s)
on (200 ms)

off

EL terminal is exchanging data, but the modules are different

off

flashing
500 ms

No AR established,
establishment of connection has not been initialized

flashing
500 ms

flashing
500 ms

Identify EL terminal through PROFINET "flashing"

LEDs starting up

Run

PN Run/Err

PN Err

Meaning

off

off

off

No electrical voltage connected to E-bus. The EL6631-0010 must be exchanged if EtherCAT terminals behind it need to function.

off

off

red on

EL terminal is starting up; after approx. 10 seconds, the LED should go out. If this does not happen, the EL6631-0010 module must be exchanged.