Standard objects (0x1000-0x1FFF)
The standard objects have the same meaning for all EtherCAT slaves.
Index 1000 Device type
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1000:0 |
Device type |
Device type of the EtherCAT slave: The Lo-Word contains the CoE profile used (5002). |
UINT32 |
RO |
0x0000138A (5002dec) |
Index 1008 Device name
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1008:0 |
Device name |
Device name of the EtherCAT slave |
STRING |
RO |
e.g. EL6601-0000-0017 |
Index 1009 Hardware version
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1009:0 |
Hardware version |
Hardware version of the EtherCAT slave |
STRING |
RO |
00 |
Index 100A Software version
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
100A:0 |
Software version |
Firmware version of the EtherCAT slave |
STRING |
RO |
00 |
Index 1600-16FE RxPDO-Map
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1600+n:0 |
RxPDO-Map |
PDO Mapping RxPDO |
UINT8 |
RW |
0x02 (2dec) |
|
(1600+n):01 |
Output Mapping Area 001 |
1. PDO Mapping Entry (Object 7000+n*8:07) |
UINT32 |
RW |
0x7000+n*8:07, 16 |
|
(1600+n):02 |
Output Mapping Area 002 |
2. PDO Mapping Entry (Object 7000+n*8:0B) |
UINT32 |
RW |
0x7000+n*8:0B, 16 |
Index 1680 PDO control
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1680:0 |
PDO control |
Max. subindex |
UINT8 |
RW |
0x01 (1dec) |
|
1680:01 |
PDO control |
Entry Master Control |
UINT32 |
RW |
0xF100:02, 16 |
Index 1A00-1AFE TxPDO-Map
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A00+n:0 |
TxPDO Map Ch.2 |
PDO Mapping TxPDO (each module gets its own entry (Index 0x1A00+n), |
UINT8 |
RW |
0x03 (3dec) |
|
(1A00+n):01 |
Input Mapping Area 001 |
1. PDO Mapping Entry (Object 0x6000+n*8:03) |
UINT32 |
RW |
0x6000+n*8:03, 16 |
|
(1A00+n):02 |
Input Mapping Area 002 |
2. PDO Mapping Entry (Object 0x6000+n*8:04) |
UINT32 |
RW |
0x6000+n*8:04, 16 |
|
(1A00+n):03 |
Input Mapping Area 003 |
3. PDO Mapping Entry (Object 0x6000+n*8:05) |
UINT32 |
RW |
0x6000+n*8:05, 16 |
Index 1A80 PDO status
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1680:0 |
PDO status |
Max. subindex |
UINT8 |
RW |
0x01 (1dec) |
|
1680:01 |
PDO status |
Entry Master Status |
UINT32 |
RW |
0xF100:01, 16 |
Index 1C00 Sync manager type
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1C00:0 |
Sync manager type |
Using the sync managers |
UINT8 |
RO |
0x02 (2dec) |
|
1C00:01 |
SubIndex 001 |
Sync-Manager Type Channel 1: Mailbox Write |
UINT8 |
RO |
0x01 (1dec) |
|
1C00:02 |
SubIndex 002 |
Sync-Manager Type Channel 2: Mailbox Read |
UINT8 |
RO |
0x02 (2dec) |
|
1C00:03 |
SubIndex 003 |
Sync-Manager Type Channel 3: Outputs |
UINT8 |
RO |
0x02 (2dec) |
|
1C00:04 |
SubIndex 004 |
Sync-Manager Type Channel 4: Inputs |
UINT8 |
RO |
0x02 (2dec) |
Index 1C12 RxPDO assign
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1C12:0 |
RxPDO assign |
PDO Assign Outputs |
UINT8 |
RW |
- |
|
1C32:01 |
SubIndex 001 |
1. allocated RxPDO (contains the index of the associated RxPDO mapping object) |
UINT32 |
RW |
0x1600 (5632dec) |
|
... |
|
|
|
|
|
|
1C12:80 |
SubIndex 128 |
128. allocated RxPDO (contains the index of the associated RxPDO mapping object) |
UINT32 |
RW |
0x167F (5759dec) |
|
1C12:81 |
SubIndex 129 |
PDO Control |
UINT32 |
RW |
0x1680 (5760dec) |
Index 1C13 TxPDO assign
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1C13:0 |
TxPDO assign |
PDO Assign Inputs |
UINT8 |
RW |
- |
|
1C13:01 |
SubIndex 001 |
1. allocated TxPDO (contains the index of the associated TxPDO mapping object) |
UINT32 |
RW |
0x1A00 (6656dec) |
|
... |
|
|
|
|
|
|
1C13:80 |
SubIndex 128 |
128. allocated TxPDO (contains the index of the associated TxPDO mapping object) |
UINT32 |
RW |
0x1A7F (6783dec) |
|
1C13:81 |
SubIndex 129 |
PDO status |
UINT32 |
RW |
0x1A80 (6784dec) |
Index 1C32 SM output parameter (only with network variables)
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1C32:0 |
SM output parameter |
Synchronization parameters for the outputs |
UINT8 |
RW |
0x0E (14dec) |
|
1C32:01 |
Sync mode |
Current synchronization mode:
|
UINT16 |
RW |
0x0001 (1dec) |
|
1C32:02 |
Cycle time |
Cycle time (in ns):
|
UINT32 |
RW |
0x00000000 (0dec) |
|
1C32:03 |
Shift time |
Time between SYNC0 event and output of the outputs (in ns, DC mode only) |
UINT32 |
RW |
0x00000000 (0dec) |
|
1C32:04 |
Sync modes supported |
Supported synchronization modes:
|
UINT16 |
RW |
0x0002 (2dec) |
Index 1C33 SM input parameter (only with network variables)
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1C33:0 |
SM input parameter |
Synchronization parameters for the inputs |
UINT8 |
RW |
0x0E (14dec) |
|
1C33:01 |
Sync mode |
Current synchronization mode:
|
UINT16 |
RW |
0x0022 (34dec) |
|
1C33:02 |
Cycle time |
as 0x1C32:02 |
UINT32 |
RW |
0x00000000 (0dec) |
|
1C33:03 |
Shift time |
Time between SYNC0 event and reading of the inputs (in ns, only DC mode) |
UINT32 |
RW |
0x00000000 (0dec) |
|
1C33:04 |
Sync modes supported |
Supported synchronization modes:
|
UINT16 |
RW |
0x0002 (2dec) |