Configuration data

Index 0x80n0 HART Settings (8 ≤ n ≤ B, n-7 = channel number)

Index (hex)

Name

Meaning

Data type

Flags

Default

80n0:0

HART Settings

Maximum subindex

UINT8

RO

0x06 (6dez)

80n0:01

Preamble

Preamble length:

UINT8

RW

0x00 (0dez)

Automatic allocation

0

allowed values

5…20

80n0:02

MasterMode

allowed values:

UINT8

RW

0x00 (0dez)

Primary

0

Secondary

1

80n0:03

PollingAddress

allowed values:

0…63

UINT8

RW

0x00 (0dez)

80n0:04

PollingTime

Unit in seconds

UINT8

RW

0x03 (3dez)

allowed values:

1…64

80n0:05

MaxRetry

allowed values:

3…10

UINT8

RW

0x03 (3dez)

80n0:06

MasterCtrl

reserved

UINT8

RW

0x00 (0dez)