EL6184 – connection and LEDs

EL6184 – connection and LEDs 1:Fig.4: EL6184 – connection and LEDs

EL6184 – connection

Terminal point

Description

Name

No.

I1

1

Input channel 1

GND

2

Ground for channel 1 (internally connected to terminal points 3, 6, and 7)

GND

3

Ground for channel 3 (internally connected to terminal points 2, 6, and 7)

I3

4

Input channel 3

I2

5

Input channel 2

GND

6

Ground for channel 2 (internally connected to terminal points 2, 3, and 7)

GND

7

Ground for channel 4 (internally connected to terminal points 2, 3, and 6)

I4

8

Input channel 4

EL6184 – LEDs

LED

Color

Meaning

Run

green

This LED indicates the terminal's operating state:

off

State of the EtherCAT State Machine: INIT = initialization of the terminal or BOOTSTRAP = function for firmware updates of the terminal

flashing

State of the EtherCAT State Machine: PREOP = function for mailbox communication and different standard-settings set

single flash

State of the EtherCAT State Machine: SAFEOP = verification of the Sync-Managers channels and the distributed clocks.
Outputs remain in safe state

on

State of the EtherCAT State Machine: OP = normal operating state; mailbox and process data communication is possible

HART-Error
1…4

green

off

No HART communication

on

HART communication active

red

off

No HART communication error

on

HART communication error