Technical data

Technical data

EL6002

EL6022

Data transfer channels

2, TxD and RxD, full duplex

2, TXD and RXD, full/half duplex

Connection

2 x D-sub connector (DE9), 9-pin

2 x D-sub connector (DE9), 9-pin

Data transfer rate

300...115200 baud
default: 9600 baud, 8 data bits, no parity, 1 stop bit

Data buffer

864 byte receive buffer, 128 byte transmit buffer per channel

Level interface

RS232

RS485/422

Cable length

max. 15 m

max. 1000 m (Twisted Pair)

Providing external supply

-

2x typ. 5 V (± 20%),
from E-bus supply (electrically isolated), max. 20 mA,
short-circuit-proof

Diagnosis

Status LEDs

Power supply

via the E-bus

Current consumption via E-bus

typ. 170 mA

typ. 250 mA
(in case of short circuit: typ. 250 mA)

Electrical isolation

500 V (E-bus/RS232C)

500 V (E-bus/RS422, E-bus/RS485)

Bit width in process image

1 x 16 bit Control/Status, Inputs/Outputs: 22 x 8 bit user data

Configuration

no address setting required
configuration via TwinCAT System Manager

Permissible ambient temperature range during operation

-25°C ... +60°C

Permissible ambient temperature range during storage

-40°C ... +85°C

Permissible relative humidity

95%, no condensation

Weight

approx. 70 g

Dimensions (W x H x D)

approx. 26 mm x 100 mm x 52 mm (width aligned: 23 mm)

Mounting

on 35 mm mounting rail conforms to EN 60715

Vibration/shock resistance

conforms to EN 60068-2-6 / EN 60068-2-27

EMC immunity/emission

conforms to EN 61000-6-2 / EN 61000-6-4

Protection class

IP20

Installation position

variable

Approvals / markings*

CE, cULus, UKCA, EAC, ATEX, IECEx,

*) Real applicable approvals/markings see type plate on the side (product marking).

Ex markings

Standard

Marking

ATEX

II 3 G Ex ec IIC T4 Gc

IECEx

Ex ec IIC T4 Gc