Technical data
Technical data | EL6021-0021 |
|---|---|
Data transfer channels | TxD and RxD, full/half duplex |
Data transfer rate | 2400...115200 baud, |
Data buffer | 864 byte receive buffer, 128 byte transmit buffer |
Special features | enlarged bias resistors |
Bit transfer | with differential signal |
Level interface | RS485/422 |
Bit distortion | - |
Cable length | max. 1000 m (Twisted Pair) |
Line impedance | 120 Ω |
Providing external supply | - |
Diagnosis | Status LEDs |
Power supply | via the E-bus |
Current consumption via E-bus | typ. 170 mA (in case of short circuit: typ. 250 mA) |
Electrical isolation | 500 V (E-bus/RS422, E-bus/RS485) |
Bit width in process image | 1 x 8 bit Control/Status, Inputs/Outputs: 3 x 8 bit user data or |
Configuration | no address setting required |
Weight | approx. 55 g |
Permissible ambient temperature range during operation | 0°C ... +55°C |
Permissible ambient temperature range during storage | -25°C ... +85°C |
Permissible relative humidity | 95%, no condensation |
Dimensions (W x H x D) | approx. 15 mm x 100 mm x 70 mm (width aligned: 12 mm) |
on 35 mm mounting rail conforms to EN 60715 | |
Enhanced mechanical load capacity | Yes, see installation instructions for enhanced mechanical load capacity |
Vibration / shock resistance | conforms to EN 60068-2-6 / EN 60068-2-27 |
EMC immunity / emission | conforms to EN 61000-6-2 / EN 61000-6-4 |
Protection class | IP20 |
Installation position | variable |
Approvals / markings* |
*) Real applicable approvals/markings see type plate on the side (product marking).
Ex markings
Standard | Marking |
|---|---|
ATEX | II 3 G Ex nA IIC T4 Gc |
IECEx | Ex nA IIC T4 Gc |