EL5151-0021 - LEDs and pin assignment

EL5151-0021 - LEDs and pin assignment 1:
EL5151-0021 - LEDs and pin assignment

EL5151-0021 - LEDs

LED

Color

Meaning

A, B, C

green

flashes when pulses are present at the inputs

Latch

green

lights up when a signal is present at the latch input

Output 1

green

Lights up when the input is set (24 VDC)

EL5151-0021 - Pin assignment

Terminal point

No.

Comment

A

1

Encoder input A

Output 1

2

0 V, 24 V

0 V

3

0 V (internally connected to terminal point 7 and negative power contact)

C

4

Encoder input C

B

5

Encoder input B

+24 V

6

+24 V (internally connected to the positive power contact)

0 V

7

0 V (internally connected to terminal point 3 and negative power contact)

Latch 24 V

8

Latch input