EL5151-00x0 - LEDs and pin assignment
Fig.29: EL5151, EL5151-0090 - LEDs and pin assignmentEL5151, EL5151-0090 - LEDs
LED | Color | Meaning |
|---|---|---|
A, B, C | green | flashes when pulses are present at the inputs |
Gate, Latch | green | lights up when a signal is present at the gate/latch input |
EL5151, EL5151-0090 - Pin assignment
Terminal point | No. | Comment |
|---|---|---|
A | 1 | Encoder input A |
+24 V | 2 | +24 V (internally connected to terminal point 6 and positive power contact) |
0 V | 3 | 0 V (internally connected to terminal point 7 and negative power contact) |
C | 4 | Encoder input C |
B | 5 | Encoder input B |
+24 V | 6 | +24 V (internally connected to terminal point 2 and positive power contact) |
0 V | 7 | 0 V (internally connected to terminal point 3 and negative power contact) |
Gate/Latch 24 V | 8 | Gate/Latch input |