Output data
Index 7000 ENC Outputs Ch.1
Index (hex)  | Name  | Meaning  | Data type  | Flags  | Default  | 
|---|---|---|---|---|---|
7000:0  | ENC Outputs Ch.1  | Maximum subindex  | UINT8  | RO  | 0x11 (17dec)  | 
7000:01  | Enable saving via the zero pulse C input.  | BOOLEAN  | RO  | 0x00 (0dec)  | |
7000:02  | Enable saving via the Latch extern input with positive edge.  | BOOLEAN  | RO  | 0x00 (0dec)  | |
7000:03  | Set counter value  | BOOLEAN  | RO  | 0x00 (0dec)  | |
7000:04  | Enable saving via the Latch extern input with negative edge.  | BOOLEAN  | RO  | 0x00 (0dec)  | |
7000:08  | Enable counter value specification via the zero pulse C input  | BOOLEAN  | RO  | 0x00 (0dec)  | |
7000:09  | Locks the counter via a PLC variable 0: Counter is unlocked 1: Counter is locked  | BOOLEAN  | RO  | 0x00 (0dec)  | |
7000:0A  | Activates the counter value specification via a positive edge at the Latch extern input.  | BOOLEAN  | RO  | 0x00 (0dec)  | |
7000:0B  | Activates the counter value specification via a negative edge at the Latch extern input.  | BOOLEAN  | RO  | 0x00 (0dec)  | |
7000:0C  | Enable saving via the Gate/Latch input with positive edge.  | BOOLEAN  | RO  | 0x00 (0dec)  | |
7000:0D  | Enable saving via the Gate/Latch input with negative edge.  | BOOLEAN  | RO  | 0x00 (0dec)  | |
7000:11  | The counter value to be set via "Set counter" (index 0x7000:03).  | UINT32  | RO  | 0x00000000 (0dec)  | 
Index 70n1 ENC Control Output Ch.n (for n = 0 [output 1], n = 1 [output 2])
Index (hex)  | Name  | Meaning  | Data type  | Flags  | Default  | 
|---|---|---|---|---|---|
70n1:0  | ENC Control Output Ch.n  | Maximum subindex  | UINT8  | RO  | 0x05 (5dec)  | 
70n1:01  | Set output via PLC  | BOOLEAN  | RO  | 0x00 (0dec)  | |
70n1:02  | Enable automatic switching function for the output. As soon as this is enabled, the preset switching state is ignored via the PLC variable.  | BOOLEAN  | RO  | 0x00 (0dec)  | |
70n1:03  | Set output via PLC  | BOOLEAN  | RO  | 0x00 (0dec)  | |
70n1:04  | Setting the bit disables the counting direction (forward): 0: Counting direction active (default)  | BOOLEAN  | RO  | 0x00 (0dec)  | |
70n1:05  | By setting the bit, the counting direction (backward) is disabled: 0: Counting direction active (default)  | BOOLEAN  | RO  | 0x00 (0dec)  | 
Index 70n2 ENC Control 2 Output Ch.n (for n = 0 [output 1], n = 1 [output 2])
Index (hex)  | Name  | Meaning  | Data type  | Flags  | Default  | 
|---|---|---|---|---|---|
70n2:0  | ENC Control 2 Output Ch.n  | Maximum subindex  | UINT8  | RO  | 0x11 (17dec)  | 
70n2:11  | Number of output events  | Enter the number of currently valid threshold values. The value should be ≥ 1 to activate the first threshold.  | UINT8  | RO  | 0x00 (0dec)  | 
Index 70n3 ENC Output States Ch.n (for n = 0 [output 1], n = 1 [output 2])
Index (hex)  | Name  | Meaning  | Data type  | Flags  | Default  | 
|---|---|---|---|---|---|
70n3:0  | ENC Output states Ch.n  | Maximum subindex  | UINT8  | RO  | 0x08 (8dec)  | 
70n3:01  | Input of the status which the output should assume when "Threshold 1” (0x70n4:11) is reached.  | BOOLEAN  | RO  | 0x00 (0dec)  | |
70n3:02  | Input of the status which the output should assume when "Threshold 2” (0x70n4:12) is reached.  | BOOLEAN  | RO  | 0x00 (0dec)  | |
70n3:03  | Input of the status which the output should assume when "Threshold 3" (0x70n4:13) is reached.  | BOOLEAN  | RO  | 0x00 (0dec)  | |
70n3:04  | Input of the status which the output should assume when "Threshold 4" (0x70n4:14) is reached.  | BOOLEAN  | RO  | 0x00 (0dec)  | |
70n3:05  | Input of the status which the output is to assume when "Threshold 5" is reached.  | BOOLEAN  | RO  | 0x00 (0dec)  | |
70n3:06  | Input of the status which the output is to assume when "Threshold 6" is reached.  | BOOLEAN  | RO  | 0x00 (0dec)  | |
70n3:07  | Input of the status which the output is to assume when "Threshold 7" is reached.  | BOOLEAN  | RO  | 0x00 (0dec)  | |
70n3:08  | Input of the status which the output is to assume when "Threshold 8" is reached.  | BOOLEAN  | RO  | 0x00 (0dec)  | 
Index 70n4 ENC Threshold Output Ch.n (for n = 0 [output 1], n = 1 [output 2])
Index (hex)  | Name  | Meaning  | Data type  | Flags  | Default  | 
|---|---|---|---|---|---|
70n4:0  | ENC Threshold Output Ch.n  | Maximum subindex  | UINT8  | RO  | 0x11 (17dec)  | 
70n4:11  | Threshold value 1 (32-bit)  | UINT32  | RO  | 0x00000000 (0dec)  | |
70n4:12  | Threshold value 2 (32-bit)  | UINT32  | RO  | 0x00000000 (0dec)  | |
70n4:13  | Threshold value 3 (32-bit)  | UINT32  | RO  | 0x00000000 (0dec)  | |
70n4:14  | Threshold value 4 (32-bit)  | UINT32  | RO  | 0x00000000 (0dec)  | |
70n4:15  | Threshold value 5 (32-bit)  | UINT32  | RO  | 0x00000000 (0dec)  | |
70n4:16  | Threshold value 6 (32-bit)  | UINT32  | RO  | 0x00000000 (0dec)  | |
70n4:17  | Threshold value 7 (32-bit)  | UINT32  | RO  | 0x00000000 (0dec)  | |
70n4:18  | Threshold value 8 (32-bit)  | UINT32  | RO  | 0x00000000 (0dec)  | 
Index 70n5 ENC Duration Output Ch.n (for n = 0 [output 1], n = 1 [output 2])
Index (hex)  | Name  | Meaning  | Data type  | Flags  | Default  | 
|---|---|---|---|---|---|
70n5:0  | ENC Duration Output Ch.n  | Maximum subindex  | UINT8  | RO  | 0x11 (17dec)  | 
70n5:11  | Switching duration in µs for which the output is to be switched when the value specified in "Threshold 1" (0x70n4:11) has been reached. 0: Status of the output remains until the next "Threshold" value is reached. Maximum switching duration: 24,000 µs  | UINT32  | RO  | 0x00000000 (0dec)  | |
70n5:12  | Switching duration in µs for which the output is to be switched when the value specified in "Threshold 2" (0x70n4:12) has been reached. 0: Status of the output remains until the next "Threshold" value is reached. Maximum switching duration: 24,000 µs  | UINT32  | RO  | 0x00000000 (0dec)  | |
70n5:13  | Switching duration in µs for which the output is to be switched when the value specified in "Threshold 3" (0x70n4:13) has been reached. 0: Status of the output remains until the next "Threshold" value is reached. Maximum switching duration: 24,000 µs  | UINT32  | RO  | 0x00000000 (0dec)  | |
70n5:14  | Switching duration in µs for which the output is to be switched when the value specified in "Threshold 4" (0x70n4:14) has been reached. 0: Status of the output remains until the next "Threshold" value is reached. Maximum switching duration: 24,000 µs  | UINT32  | RO  | 0x00000000 (0dec)  | |
70n5:15  | Switching duration in µs for which the output is to be switched when the value specified in "Threshold 5" (0x70n4:15) has been reached. 0: Status of the output remains until the next "Threshold" value is reached. Maximum switching duration: 24,000 µs  | UINT32  | RO  | 0x00000000 (0dec)  | |
70n5:16  | Switching duration in µs for which the output is to be switched when the value specified in "Threshold 6" (0x70n4:16) has been reached. 0: Status of the output remains until the next "Threshold" value is reached. Maximum switching duration: 24,000 µs  | UINT32  | RO  | 0x00000000 (0dec)  | |
70n5:17  | Switching duration in µs for which the output is to be switched when the value specified in "Threshold 7" (0x70n4:17) has been reached. 0: Status of the output remains until the next "Threshold" value is reached. Maximum switching duration: 24,000 µs  | UINT32  | RO  | 0x00000000 (0dec)  | |
70n5:18  | Switching duration in µs for which the output is to be switched when the value specified in "Threshold 8" (0x70n4:18) has been reached. 0: Status of the output remains until the next "Threshold" value is reached. Maximum switching duration: 24,000 µs  | UINT32  | RO  | 0x00000000 (0dec)  |