Selection of encoder type (Counter mode)
To ensure a correct acquisition of the counter value, you must first select the appropriate encoder type.
The connected encoder is selected via index 0x80n1:1D "Counter mode". Explanations of the supported encoder and signal types can be found in chapter "Supported Encoder / Signal Types".
Selection of encoder type via index 0x80n1:1D “Counter mode”  | |
|---|---|
Value  | Meaning  | 
0: Encoder RS422 (diff. input)  | RS422 encoder with or without zero pulse  | 
1: Counter RS422 (diff. input)  | RS422 counter/pulse generator, with or without zero pulse,  | 
2: Encoder TTL (single-ended)  | TTL encoder with or without zero pulse  | 
3: Counter TTL (single-ended)  | TTL counter/pulse generator with or without zero pulse,  | 
4: Encoder open collector  | Open Collector encoder with or without zero pulse  | 
5: Counter open collector  | Open Collector counter/pulse generator with or without zero pulse,  | 
In the following sections, the settings under subindices 0, 2 and 4 are generally referred to as "encoder" and the settings under subindices 1, 3 and 5 as "counter/pulse generator".
![]()  | Activating error detection for the C track In delivery state, error detection on the C track is switched off; the default setting for index 0x80n0:0D "Error detection C" is FALSE. If an encoder or counter/pulse generator with zero pulse C is used, index 0x80n0:0D "Error detection C" can be set to TRUE at the module. The corresponding LED will then also indicate the error.  | 