EL5112 - LEDs
Single-channel mode (1xABC)
 Fig.40: EL5112 - LEDs in single-channel mode
Fig.40: EL5112 - LEDs in single-channel mode| No. | Name | Color | Description | |
|---|---|---|---|---|
| 1 | A1 | green, red | Green: indicates TRUE level Red: There is a broken wire at the respective input. Diagnosis is only possible if the following three conditions are met. 
 | |
| 2 | B1 | |||
| 3 | C1 | |||
| 4 | Status Input | red | Fault signal input from encoder. Input is internally connected to 5 V via a pull-up resistor. The encoder output must actively pull the signal against GND. | |
| on | Output active at the encoder, a fault message is present at the encoder | |||
| off | Output not active at the encoder; no fault message is present | |||
| 5 | PowerEnc. | green | Operating voltage display for incremental encoder power supply | |
| 7 | Latch | green | is lit, if a signal (+24 V) is connected to the latch input | |
| 9 | Run | green | This LED indicates the terminal's operating state: | |
| off | State of the EtherCAT State Machine: INIT = initialization of the terminal or BOOTSTRAP = function for firmware updates of the terminal | |||
| flashing | State of the EtherCAT State Machine: PREOP = function for mailbox communication and different default settings set | |||
| Single flash | State of the EtherCAT State Machine: SAFEOP = verification of the Sync Manager channels and the distributed clocks. Outputs remain in safe state | |||
| on | State of the EtherCAT State Machine: OP = normal operating state; mailbox and process data communication is possible | |||
| 10 | Diag | red | Initialization process active or state of the EtherCAT State Machine: BOOT | |
| 15 | Gate/Latch | green | is lit if a signal (+24 V) is present at the gate/latch input | |
Two-channel mode (2xAB)
 Fig.41: EL5112 - LEDs in two-channel mode
Fig.41: EL5112 - LEDs in two-channel mode| No. | Name | Color | Description | |
|---|---|---|---|---|
| 1 | A1 | green, red | Green: indicates TRUE level Red: There is a broken wire at the respective input. Diagnosis is only possible if the following three conditions are met. 
 | |
| 2 | B1 | |||
| 3 | A2 | |||
| 4 | B2 | |||
| 5 | PowerEnc. | green | Operating voltage display for incremental encoder power supply | |
| 7 | Latch | green | is lit, if a signal (+24 V) is connected to the latch input | |
| 9 | Run | green | This LED indicates the terminal's operating state: | |
| off | State of the EtherCAT State Machine: INIT = initialization of the terminal or BOOTSTRAP = function for firmware updates of the terminal | |||
| flashing | State of the EtherCAT State Machine: PREOP = function for mailbox communication and different default settings set | |||
| Single flash | State of the EtherCAT State Machine: SAFEOP = verification of the Sync Manager channels and the distributed clocks. Outputs remain in safe state | |||
| on | State of the EtherCAT State Machine: OP = normal operating state; mailbox and process data communication is possible | |||
| 10 | Diag | red | Initialization process active or state of the EtherCAT State Machine: BOOT | |
| 15 | Gate/Latch | green | is lit if a signal (+24 V) is present at the gate/latch input | |