Selection of encoder type (Counter mode)
To ensure a correct acquisition of the counter value, you must first select the appropriate encoder type.
The connected encoder is selected via index 0x80n1:1D "Counter mode". Explanations of the supported encoder and signal types can be found in chapter "Supported Encoder / Signal Types".
Selection of encoder type via index 0x80n1:1D “Counter mode” | |
|---|---|
Value | Meaning |
0: Encoder RS422 (diff. input) | RS422 encoder with or without zero pulse |
1: Counter RS422 (diff. input) | RS422 counter/pulse generator, with or without zero pulse, |
2: Encoder TTL (single-ended) | TTL encoder with or without zero pulse |
3: Counter TTL (single-ended) | TTL counter/pulse generator with or without zero pulse, |
4: Encoder open collector | Open Collector encoder with or without zero pulse |
5: Counter open collector | Open Collector counter/pulse generator with or without zero pulse, |
In the following sections, the settings under subindices 0, 2 and 4 are generally referred to as "encoder" and the settings under subindices 1, 3 and 5 as "counter/pulse generator".
![]() | Activating error detection for the C track In delivery state, error detection on the C track is switched off; the default setting for index 0x80n0:0D "Error detection C" is FALSE. If an encoder or counter/pulse generator with zero pulse C is used, index 0x80n0:0D "Error detection C" can be set to TRUE at the module. The corresponding LED will then also indicate the error. |
