Wiring
| |
Risk of electric shock and damage of device! Bring the bus terminal system into a safe, powered down state before starting installation, disassembly or wiring of the bus terminals! |
Terminals for standard wiring ELxxxx/KLxxxx and for pluggable wiring ESxxxx/KSxxxx
![Wiring 1:](Images/png/3987644299__Web.png)
Up to eight terminal points enable the connection of solid or finely stranded cables to the bus terminal. The terminal points are implemented in spring force technology. Connect the cables as follows:
- Open a terminal point by pushing a screwdriver straight against the stop into the square opening above the terminal point. Do not turn the screwdriver or move it alternately (don't toggle).
- The wire can now be inserted into the round terminal opening without any force.
- The terminal point closes automatically when the pressure is released, holding the wire securely and permanently.
See the following table for the suitable wire size width.
Terminal housing | ELxxxx, KLxxxx | ESxxxx, KSxxxx |
Wire size width (single core wires) | 0.08 ... 2.5 mm2 | 0.08 ... 2.5 mm2 |
Wire size width (fine-wire conductors) | 0.08 ... 2.5 mm2 | 0.08 ... 2.5 mm2 |
Wire size width (conductors with a wire end sleeve) | 0.14 ... 1.5 mm2 | 0.14 ... 1.5 mm2 |
Wire stripping length | 8 ... 9 mm | 9 ... 10 mm |
High Density Terminals (HD Terminals) with 16 terminal points
The conductors of the HD Terminals are connected without tools for single-wire conductors using the direct plug-in technique, i.e. after stripping the wire is simply plugged into the terminal point. The cables are released, as usual, using the contact release with the aid of a screwdriver. See the following table for the suitable wire size width.
Terminal housing | High Density Housing |
Wire size width (single core wires) | 0.08 ... 1.5 mm2 |
Wire size width (fine-wire conductors) | 0.25 ... 1.5 mm2 |
Wire size width (conductors with a wire end sleeve) | 0.14 ... 0.75 mm2 |
Wire size width (ultrasonically “bonded" conductors) | only 1.5 mm2 (see notice) |
Wire stripping length | 8 ... 9 mm |