Technical data

Technical data

EL4712

EL4732

Number of outputs

2

Signal voltage

0 mA ... 20 mA

-10 V ... +10 V

Oversampling factor

n = integer multiple of the EtherCAT cycle time, configurable between 1 and 100

Distributed Clocks precision

< 100 ns

Load

< 500 Ω (short-circuit-proof)

> 5 kΩ (short-circuit-proof)

Resolution

16 bit (including sign)

Sampling type

simultaneous

Ground reference

single ended

Conversion time

~ 10 µs

Output rate

max. 100 ksamples/s

Measuring error

< ± 0.1% (in relation to the output end value)

< ± 0.1% (at 0 °C ... +55 °C, relative to the full scale value)
< ± 0.2% (when the extended temperature range is used)

Electrical isolation

500 V (E-bus/field voltage)

Supply voltage for electronics

via E-bus

Current consumption power contacts

typ. 20 mA + load

-

Power supply for outputs

via 24 V power contacts

via E-bus

Current consumption via E-bus

typ. 100 mA

typ. 180 mA

Largest short-term deviation during a specified electrical interference test

5 %

Bit width in process image

Output: n x 2 x 16 bit data, 2 x 16 bit CycleCounter, 4 byte StartTimeNextOutput, if required

Configuration

via TwinCAT System Manager

Weight

approx. 65 g

approx. 50 g

Permissible ambient temperature range during operation

0°C ... + 55°C

-25°C ... +60°C

Permissible ambient temperature range during storage

-25°C ... + 85°C

-40°C ... +85°C

Permissible relative humidity

95 %, no condensation

95 %, no condensation

Dimensions (W x H x D)

approx. 15 mm x 100 mm x 70 mm (width aligned: 12 mm)

Mounting

on 35 mm mounting rail conforms to EN 60715

Enhanced mechanical load capacity

yes, see also installation instructions for enhanced mechanical load capacity

Vibration/shock resistance

conforms to EN 60068-2-6 / EN 60068-2-27

EMC immunity/emission

conforms to EN 61000-6-2 / EN 61000-6-4

Protection class

IP20

Installation position

variable

Marking / Approval*)

CE, UKCA, EAC, CCC
cULus, ATEX, IECEx

CE, UKCA, EAC, CCC
cULus, ATEX, IECEx, cFMus

*) Real applicable approvals/markings see type plate on the side (product marking).

Ex markings

Standard

Marking

ATEX

II 3 G Ex ec IIC T4 Gc

IECEx

Ex ec IIC T4 Gc

cFMus

Class I, Division 2, Groups A, B, C, D
Class I, Zone 2, AEx/Ex ec IIC T4 Gc