Instructions for use
Parallel connection in current mode
The current outputs of the EL4374 are single-ended and can be connected in parallel to add their currents to the load. For full output of both channels, the load resistance must not exceed 375 ohms.
Note: Ohm's law must be observed, the internally available output voltage does not increase!
Output behavior, rise time
You can expect approx. 3 ms for 0->90% and approx. 6 ms for 0->100%

Output behavior, dynamics
The output behavior is designed for a dynamic range of 2 ksps/500 µs (setpoint specification). This means that low dynamic signals are output. The output terminals of the EL41xx series are recommended for the output of frequencies above 200 Hz.
Spontaneous output when switching on/off ("glitch")
When the Us supply (E-bus) is switched on or spontaneously switched off and on again, there may be brief, independent value output in the range of a few ±10% of the FSV for a few ms.
When the Up supply (power contacts) is switched on or spontaneously switched off and on again, there may be brief, independent value output in the range of a few ±% of the FSV for a few ms.
It is recommended that sensitive signal receivers only be switched to receive mode when the terminal/channel
- is in the OP state
- does not report a warning or error in the PDO state
If a glitch-free output is required, output terminals from the EL417x series can be used.