Diag-Messages

The terminal provides the following diagnosis messages, they belong together in pairs:

Diag-Code

Meaning

TwinCAT Message

Troubleshooting

#x4101

Terminal-Overtemperature

Terminal-Overtemperature

Device is too warm internally, but continues to work, provide cooling

#x170E

Device temperature is ok again

No overtemperature anymore

-

#x8601

Supply voltage too low

Supply voltage too low

Check voltage of power contacts Up

#x1180

Supply voltage is ok

Supply voltage ok

-

#x8707

Channel overload (Channel %d)

Channel overload (Channel %d)

Check wiring and load, possibly short circuit/OpenLoad?

#x1708

Channel %d is no longer overloaded

Channel %d is no longer overloaded

-

#x8144

Hardware fault %d

Hardware fault %d

Check load, measure output function externally, contact support if necessary

#x0001

no error

no error

-

Diag-Messages 1:
Fig.26: Display in TwinCAT 3.1