Presentation function

Presentation function 1:Fig.152: Block diagram for determining the output values with default settings (presentation function)

The presentation function block according to index 0x80x0:02 converts the PDO value into the internal SINT16 format (signed integer, 16-bit) for further calculation and DAC output, depending on the setting. Depending on the presentation selected, the following applies:

Signed presentation (default setting)

Output signal

Value

EL4102

Decimal

Hexadecimal

0 V

0

0x0000

5 V

16383

0x3FFF

10 V

32767

0x7FFF

Output signal

Value

EL4112

Decimal

Hexadecimal

0 mA

0

0x0000

10 mA

16383

0x3FFF

20 mA

32767

0x7FFF

Output signal

Value

EL4112-0010

Decimal

Hexadecimal

-10 mA

-32768

0x8000

-5 mA

-16383

0xC001

0 mA

0

0x0000

5 mA

16383

0x3FFF

10 mA

32767

0x7FFF

Output signal

Value

EL4122

Decimal

Hexadecimal

4 mA

0

0x0000

12 mA

16383

0x3FFF

20 mA

32767

0x7FFF

Output signal

Value

EL4132

Decimal

Hexadecimal

-10 V

-32768

0x8000

-5 V

-16383

0xC001

0 V

0

0x0000

5 V

16383

0x3FFF

10 V

32767

0x7FFF

Unsigned presentation

Absolute value with MSB as sign

Absolute value

Examples of the presentations