EL4122 - Technical data

Technical data

EL4122

Number of outputs

2

Output current per channel

4 ... 20 mA
(short-circuit proof)

Accuracy

± 0.1%
of full-scale value

Resolution

16 bits (including sign)

Sampling type

simultaneous

Ground reference

single ended

Load

< 500 Ω

Distributed Clocks (DC)

Yes, from EL4122-0000-1017

Max. sampling rate (output rate)

DC disabled **)

Normal operation: 10 kSps (corresponds to minimum EtherCAT cycle time of 100 µs)

Fast mode: 15 kSps (corresponds to minimum EtherCAT cycle time of 66.6 µs)

Fast mode 1-channel: 20 kSps (corresponds to minimum EtherCAT cycle time of 50 µs)

DC enabled

Normal operation: 5 kSps (corresponds to minimum EtherCAT cycle time of 200 µs)

Fast mode: not possible

Power supply for outputs

via the power contacts

Current consumption power contacts

15 mA typ. + load

Power supply for the electronics

via the E-bus

Current consumption via E-bus

typ. 110 mA (160 mA***))

Electrical isolation

500 V (E-bus/field voltage)

Bit width in process image

Outputs: 2 x 16 bit data

Configuration

no address or configuration settings required

Weight

approx. 60 g

Permissible ambient temperature range during operation

0 °C ... +55 °C

Permissible ambient temperature range during storage

-25 °C ... +85 °C

Permissible relative air humidity

95 %, no condensation

Dimensions (W x H x D)

approx. 15 mm x 100 mm x 70 mm (width aligned: 12 mm)

Installation

on 35 mm mounting rail, conforms to EN 60715

Vibration / shock resistance

conforms to EN 60068-2-6 / EN 60068-2-27
see also Installation instructions for enhanced mechanical load capacity

EMC immunity / emission

conforms to EN 61000-6-2 / EN 61000-6-4

Protection rating

IP20

Installation position

variable

Identification / approval*)

CE, EAC, UKCA
ATEX, IECEx, cULus

*) Real applicable approvals/markings see type plate on the side (product marking).

**) SyncManager-synchronous, EtherCAT frame-triggered
The EL41xx does not support oversampling, therefore the output rate is equal to the EtherCAT cycle time.

***) valid for HW / FW / revision combinations before HW 12 / FW 09, Rev.-1021

Ex markings

Standard

Marking

ATEX

II 3 G Ex nA IIC T4 Gc

IECEx

Ex nA IIC T4 Gc