EL4014

EL4014 1:
EL4014, Connection and display

Connection EL4014

Terminal point

No.

Comment

Internally connected with connector

Max. current carrying capacity*)

Output 1

1

Output 1

-

Specified by output power

Ground

2

0 V

4, 6, 8

500 mA

Output 3

3

Output 3

-

Specified by output power

Ground

4

0 V

2, 6, 8

500 mA

Output 2

5

Output 2

-

Specified by output power

Ground

6

0 V

2, 4, 8

500 mA

Output 4

7

Output 4

-

Specified by output power

Ground

8

0 V

2, 4, 6

500 mA

*) Constant and peak value

LEDs EL4014

LED

Color

Meaning

RUN

green

This LED indicates the terminal's operating state:

off

State of the EtherCAT State Machine: INIT = initialization of the terminal, state of the EtherCAT State Machine: BOOTSTRAP = function for firmware updates of the terminal

flashing

State of the EtherCAT State Machine: PREOP = function for mailbox communication and different standard-settings set

single flash

State of the EtherCAT State Machine: SAFEOP = verification of the Sync Manager channels and the distributed clocks.
Outputs remain in safe state

on

State of the EtherCAT State Machine: OP = normal operating state; mailbox and process data communication is possible

If several RUN LEDs are present, all of them have the same function.