Output data

Index 70n0 AO Outputs*)

Index (hex)

Name

Meaning

Data type

Flags

Default

70n0:0

AI Outputs

Maximum subindex

UINT8

RO

0x14 (20dec)

70n0:11

Value

Analog output value

INT16

RO

0x0000 (0dec)

70n0:13

Value (Real32)

Analog output value (Real32)

REAL32

RO

0x00000000 (0dec)

70n0:14

Output Cycle Counter

The counter is incremented each time the output data in the process image is updated.

UINT16

RO

0x0000 (0dec)

*) EL4072 (Ch.1 - 2): 0 ≤ n ≤ 1; EL4074 (Ch.1 – 4): 0 ≤ n ≤ 3; EL4078 (Ch.1 – 8): 0 ≤ n ≤ 7