Technical data EL407x
Technical data | EL4072 | EL4074 | EL4078 |
|---|---|---|---|
Number of outputs | 2 | 4 | 8 |
Wiring | 2-wire | ||
Ground reference | single-ended | ||
Max. sampling rate | min. 500 µs (max. 2 ksps) per channel | ||
Sampling type | Multiplex, approx. 25 µs delay between channels n/n+1 | ||
Load | Voltage: > 2 kΩ (short-circuit proof) | Voltage: > 2 kΩ (short-circuit proof) | Voltage: > 2 kΩ (short-circuit proof) |
Output range, nominal | -10 V / 0 V…+10 V | ||
Output end value (AEW, FSV) | 10 V / 20 mA | ||
Output range, technical | -10.73 V…+10.73 V Observe note 1) | ||
Resolution | 16 bit (including sign) | ||
Output error / uncertainty | < ±0.07 %AEW typ. (voltage and current, at 25 °C ±5 °C, otherwise < ±0.1 %AEW, with averaging) 2) | ||
Temperature coefficient | TkGain: 10 ppm/K typ. 2) | ||
Noise | Voltage: ±0.005 %AEW typ. (in the range 0..5 kHz) 2) | ||
Channel crosstalk | Voltage: < -70 dB typ. 2) | ||
Load type | Ohmic | ||
Electrical isolation channel/channel | no | ||
1) EL4078: if more than 4 channels are configured for current output, the remaining voltage channels can only be controlled up to max. ±5 V for thermal reasons. 2) Preliminary information |
Technical data | General | |||
|---|---|---|---|---|
Power supply | via power contacts, 24 V DC (-15 % / +20 %) | |||
Distributed clocks | – | |||
Electrical isolation channel/SGND | functional separation 707 V DC (type test) | |||
Electrical isolation channel/E-bus | functional separation 707 V DC (type test) | |||
Current consumption of power contacts | 60 mA typ. (required for operation of the outputs, specification at full load, additional current requirement at +24 V/0 V connected loads) | |||
Current consumption via E-bus | 100 mA typ. | 125 mA typ. | 180 mA typ. | |
Min. EtherCAT cycle time | 50 µ | |||
Special features | 107 % measuring range/output range, output diagnostics | |||
Weight | approx. 55 g | |||
Operating/storage temperature | -25 °C…+60 °C / -40 °C…+85 °C | -25 °C…+55 °C / -40 °C…+85 °C | ||
Relative humidity | 95%, no condensation | |||
EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 | |||
Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 | |||
Protection rating/installation position | IP20/any | |||
Approvals/markings*) | CE, UKCA, EAC | |||
*) Real applicable approvals/markings see type plate on the side (product marking).