Standard objects
Index 1000 Device type
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1000:0 |
Device type |
Device type of the EtherCAT slave: the Lo-Word contains the CoE profile used (5001). The Hi-Word contains the module profile according to the modular device profile. |
UINT32 |
RO |
0x012C1389(19665801dec) |
Index 1008 Device name
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1008:0 |
Device name |
Device name of the EtherCAT slave |
STRING |
RO |
EL3773 |
Index 1009 Hardware version
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1009:0 |
Hardware version |
Hardware version of the EtherCAT slave |
STRING |
RO |
- |
Index 100A Software version
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
100A:0 |
Software version |
Firmware version of the EtherCAT slave |
STRING |
RO |
- |
Index 1018 Identity
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1018:0 |
Identity |
Information for identifying the slave |
UINT8 |
RO |
> 4 < |
|
1018:01 |
Vendor ID |
Vendor ID of the EtherCAT slave |
UINT32 |
RO |
0x00000002 |
|
1018:02 |
Product code |
Product code of the EtherCAT slave |
UINT32 |
RO |
0x0EBD3052 |
|
1018:03 |
Revision |
Revision number of the EtherCAT slave; the low word (bit 0-15) indicates the special terminal number, the high word (bit 16-31) refers to the device description |
UINT32 |
RO |
- |
|
1018:04 |
Serial number |
Serial number of the EtherCAT slave; the low byte (bit 0-7) of the low word contains the year of production, the high byte (bit 8-15) of the low word contains the week of production, the high word (bit 16-31) is 0 |
UINT32 |
RO |
0x00000000 |
Index 10F0 Backup parameter handling
|
Index |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
10F0:0 |
Backup parameter handling |
Information for standardized loading and saving of backup entries |
UINT8 |
RO |
> 1 < |
|
10F0:01 |
Checksum |
Checksum across all backup entries of the EtherCAT slave |
UINT32 |
RO |
0x00000000 (0dec) |
Index 18pp Analog Input TxPDO-Par Samples (for Ch. 1 ... Ch.6; 01hex ≤ pp ≤ 5Fhex)
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
18pp:0 |
AI TxPDO-Par Sample |
PDO Parameter TxPDO |
UINT8 |
RO |
> 6 < |
|
18pp:06 |
Exclude TxPDOs |
Specifies the TxPDOs (index of TxPDO mapping objects) that must not be transferred together with this PDO |
OCTET-STRING[2] |
RO |
Index 1Ap0 AI TxPDO-Map Status (for p = 0...5; dependent on the number of channels)
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1Ap0:0 |
AI TxPDO-Map Status |
PDO Mapping TxPDO |
UINT8 |
RO |
> 10 < |
|
1Ap0:01 |
SubIndex 001 |
1. PDO Mapping entry (object 0x60p0 (AI Inputs), entry 0x01 (Underrange)) |
UINT32 |
RO |
0x60p0:01, 1 |
|
1Ap0:02 |
SubIndex 002 |
2. PDO Mapping entry (object 0x60p0 (AI Inputs), entry 0x02 (Overrange)) |
UINT32 |
RO |
0x60p0:02, 1 |
|
1Ap0:03 |
SubIndex 003 |
3. PDO Mapping entry (object 0x60p0 (AI Inputs), entry 0x03 (Limit 1)) |
UINT32 |
RO |
0x60p0:03, 2 |
|
1Ap0:04 |
SubIndex 004 |
4. PDO Mapping entry (object 0x60p0 (AI Inputs), entry 0x05 (Limit 2)) |
UINT32 |
RO |
0x60p0:05, 2 |
|
1Ap0:05 |
SubIndex 005 |
5. PDO Mapping entry (object 0x60p0 (AI Inputs), entry 0x07 (Error)) |
UINT32 |
RO |
0x60p0:07, 1 |
|
1Ap0:06 |
SubIndex 006 |
6. PDO Mapping entry (1 bit align) |
UINT32 |
RO |
0x0000:00, 1 |
|
1Ap0:07 |
SubIndex 007 |
7. PDO Mapping entry (5 bits align) |
UINT32 |
RO |
0x0000:00, 5 |
|
1Ap0:08 |
SubIndex 008 |
8. PDO Mapping entry (object 0x60p0 (AI Inputs), entry 0x0E (Sync error)) |
UINT32 |
RO |
0x60p0:0E, 1 |
|
1Ap0:09 |
SubIndex 009 |
9. PDO Mapping entry (object 0x60p0 (AI Inputs), entry 0x0F (TxPDO State)) |
UINT32 |
RO |
0x60p0:0F, 1 |
|
1Ap0:0A |
SubIndex 010 |
10. PDO Mapping entry (object 0x60p0 (AI Inputs), entry 0x10 (TxPDO Toggle)) |
UINT32 |
RO |
0x60p0:10, 1 |
Index 1Apq AI TxPDO-Map Samples
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default | ||
|---|---|---|---|---|---|---|---|
|
1Apq:0 |
AI TxPDO-Map Samples |
n |
p |
q |
UINT8 |
RO |
> n < |
|
1dec = Max. Subindex: 001 |
0x0 = L1 Voltage Samples |
0x1 = 1 Sample 0x60p2:01, 16 | |||||
|
1Apq:hh (for 01hex ≤ hh ≤ 64hex) |
Subindex n |
Voltage Samples or Current Samples |
INT16 |
RO |
- | ||
Index 1A60 Analog Input TxPDO-Map Timestamp
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A60:0 |
AI Timestamp Next Sync1 Time |
Max. Subindex |
UINT8 |
RO |
> 1 < |
|
1A60:01 |
Subindex 001 |
1. PDO Mapping entry (object 0x6060 (AI Inputs), entry 0x01 (Next Sync1 Time)) |
UINT64 |
RO |
0x6060:01, 64 |
Index 1A61 Analog Input TxPDO-Map Sample Counter
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A60:0 |
AI Timestamp Sample Counter |
Max. Subindex |
UINT8 |
RO |
> 1 < |
|
1A61:01 |
Subindex 001 |
1. PDO Mapping entry (object 0x6061 (AI Inputs), entry 0x01 (SampleCount)) |
UINT16 |
RO |
0x6061:01, 16 |
Index 1C00 0 Sync manager type
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1C00:0 |
Sync manager type |
Using the sync managers |
UINT8 |
RO |
> 4 < |
|
1C00:01 |
SubIndex 001 |
Sync-Manager Type Channel 1: Mailbox Write |
UINT8 |
RO |
0x01 (1dec) |
|
1C00:02 |
SubIndex 002 |
Sync-Manager Type Channel 2: Mailbox Read |
UINT8 |
RO |
0x02 (2dec) |
|
1C00:03 |
SubIndex 003 |
Sync-Manager Type Channel 3: Process Data Write (Outputs) |
UINT8 |
RO |
0x03 (3dec) |
|
1C00:04 |
SubIndex 004 |
Sync-Manager Type Channel 4: Process Data Read (Inputs) |
UINT8 |
RO |
0x04 (4dec) |
Index 1C12 RxPDO assign
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1C12:0 |
RxPDO assign |
PDO Assign Outputs |
UINT8 |
RW |
> 0 < |
Index 1C13 TxPDO assign
For operation on masters other than TwinCAT it must be ensured that the channels are entered in the PDO assignment (“TxPDO assign”, object 0x1C13) successively.
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1C13:0 |
TxPDO assign |
PDO Assign Inputs |
UINT8 |
RW |
> 4 < |
|
1C13:01 |
SubIndex 001 |
1. allocated TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x1A00 (6656dec) |
|
1C13:02 |
SubIndex 002 |
2. allocated TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x1A06 (6662dec) |
|
1C13:03 |
SubIndex 003 |
3. allocated TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x1A10 (6672dec) |
|
1C13:04 |
SubIndex 004 |
4. allocated TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x1A16 (6678dec) |
|
1C13:05 |
SubIndex 005 |
5. allocated TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x1A20 (6688dec) |
|
1C13:06 |
SubIndex 006 |
6. allocated TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x1A26 (6694dec) |
|
1C13:07 |
SubIndex 007 |
7. allocated TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x1A30 (6704dec) |
|
1C13:08 |
SubIndex 008 |
8. allocated TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x1A36 (6710dec) |
|
1C13:09 |
SubIndex 009 |
9. allocated TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x1A40 (6720dec) |
|
1C13:0A |
SubIndex 010 |
10. allocated TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x1A46 (6726dec) |
|
1C13:0B |
SubIndex 011 |
11. allocated TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x1A50 (6736dec) |
|
1C13:0C |
SubIndex 012 |
12. allocated TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x1A56 (6742dec) |
|
1C13:0D |
SubIndex 013 |
13. allocated TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x1A60 (6752dec) |
|
1C13:0E |
SubIndex 014 |
14. allocated TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x1A61 (6753dec) |
Index 1C33 SM input parameter
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1C33:0 |
SM input parameter |
Synchronization parameters for the inputs |
UINT8 |
RO |
> 32 < |
|
1C33:01 |
Sync mode |
Current synchronization mode:
|
UINT16 |
RW |
0x0002 (2dec) |
|
1C33:02 |
Cycle time |
Cycle time (in ns):
|
UINT32 |
RW |
0x003D0900 (4000000dec) |
|
1C33:03 |
Shift time |
Time between SYNC0 event and reading of the inputs (in ns, only DC mode) |
UINT32 |
RO |
0x00000000 (0dec) |
|
1C33:04 |
Sync modes supported |
Supported synchronization modes:
|
UINT16 |
RO |
0x0806 (2054dec) |
|
1C33:05 |
Minimum cycle time |
Minimum cycle time (in ns) |
UINT32 |
RO |
0x000186A0 (100000dec) |
|
1C33:06 |
Calc and copy time |
Time between reading of the inputs and availability of the inputs for the master (in ns, only DC mode) |
UINT32 |
RO |
0x00000000 (0dec) |
|
1C33:08 |
Command |
With this entry the real required process data provision time can be measured.
The entries 0x1C33:03, 0x1C33:06, 0x1C33:09 are updated with the maximum measured values. |
UINT16 |
RW |
0x0000 (0dec) |
|
1C33:09 |
Maximum Delay time |
Time between SYNC1 event and reading of the inputs (in ns, only DC mode) |
UINT32 |
RO |
0x00000000 (0dec) |
|
1C33:0B |
SM event missed counter |
Number of missed SM events in OPERATIONAL (DC mode only) |
UINT16 |
RO |
0x0000 (0dec) |
|
1C33:0C |
Cycle exceeded counter |
Number of occasions the cycle time was exceeded in OPERATIONAL (cycle was not completed in time or the next cycle began too early) |
UINT16 |
RO |
0x0000 (0dec) |
|
1C33:0D |
Shift too short counter |
Number of occasions that the interval between SYNC0 and SYNC1 event was too short (DC mode only) |
UINT16 |
RO |
0x0000 (0dec) |
|
1C33:20 |
Sync error |
The synchronization was not correct in the last cycle (outputs were output too late; DC mode only) |
BOOLEAN |
RO |
FALSE |
Index F000 Modular device profile
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
F000:0 |
Modular device profile |
General information for the modular device profile |
UINT8 |
RO |
> 2 < |
|
F000:01 |
Module index distance |
Index distance of the objects of the individual channels |
UINT16 |
RO |
0x0010 (16dec) |
|
F000:02 |
Maximum number of modules |
Number of channels |
UINT16 |
RO |
0x0007 (7dec) |
Index F008 Code word
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
F008:0 |
Code word |
reserved |
UINT32 |
RW |
0x00000000 (0dec) |
Index F010 Module list
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
F010:0 |
Module list |
Maximum subindex |
UINT8 |
RW |
> 7 < |
|
F010:01 |
SubIndex 001 |
Analog input profile (300) |
UINT32 |
RW |
0x0000012C (300dec) |
|
F010:02 |
SubIndex 002 |
Analog input profile (300) |
UINT32 |
RW |
0x0000012C (300dec) |
|
F010:03 |
SubIndex 003 |
Analog input profile (300) |
UINT32 |
RW |
0x0000012C (300dec) |
|
F010:04 |
SubIndex 004 |
Analog input profile (300) |
UINT32 |
RW |
0x0000012C (300dec) |
|
F010:05 |
SubIndex 005 |
Analog input profile (300) |
UINT32 |
RW |
0x0000012C (300dec) |
|
F010:06 |
SubIndex 006 |
Analog input profile (300) |
UINT32 |
RW |
0x0000012C (300dec) |
|
F010:07 |
SubIndex 007 |
Analog input profile (300) |
UINT32 |
RW |
0x0000012C (300dec) |