Measurement ±10 mV

Measurement mode

±10 mV

Measuring range, nominal

-10…+10 mV

Measuring range, end value (full scale value)

10 mV

Measuring range, technically usable

-10.737…+10.737 mV

PDO resolution

24 bit (including sign)

PDO LSB (Extended Range)

1.28 nV

PDO LSB (Legacy Range)

1.192.. nV

Basic accuracy: Measuring deviation at 23°C, with averaging

< ±0.06%FSV = ±600 ppmFSV

Offset/Zero Point deviation (at 23°C)

EOffset

< 550 ppmFSV

Gain/scale/amplification deviation (at 23°C)

EGain

< 150 ppm

Non-linearity over the whole measuring range

ELin

< 160 ppmFSV

Repeatability

ERep

< 50 ppmFSV

Noise (without filtering)

ENoise, PtP

< 1200 ppmFSV

< 9375 [digits]

ENoise, RMS

< 200 ppmFSV

< 1563 [digits]

Max. SNR

> 74.0 dB

Noisedensity@1kHz

< 28.28 Measurement ±10 mV 1:

Noise (with 50Hz FIR filtering)

ENoise, PtP

< 120 ppmFSV

< 938 [digits]

ENoise, RMS

< 21.0 ppmFSV

< 164 [digits]

Max. SNR

> 93.6 dB

Temperature coefficient

TcGain

< 22 ppm/K typ.

TcOffset

< 20 ppmFSV/K typ.

Common-mode rejection ratio (without filtering)

DC: >115 dB typ.

50 Hz: >105 dB typ.

1 kHz: >80 dB typ.

Common-mode rejection ratio (with 50Hz FIR filtering)

DC: >115 dB typ.

50 Hz: >115 dB typ.

1 kHz: >115 dB typ.

Largest short-term deviation during a specified electrical interference test

±0.2%FSV = ±2000 ppmFSV typ.

Input impedance ±Input 1

(Internal resistance)

Differential 4.1 MΩ || 11 nF typ.

CommonMode 1 MΩ || 40 nF typ.
Methodology: Resistor against -UV, capacitance against SGND

Input impedance ±Input 2

No usage of this input in this mode

Measurement ±10 mV 2:Fig.27: Representation ±10 mV measurement range

Note: In Extended Range Mode the Underrange/Overrange display in the PDO status has the character of an information/warning when the nominal measuring range is exceeded, i.e. no Error is displayed in the PDO status and LED. If the technical measuring range is also exceeded, Error = TRUE is also displayed. The detection limit for Underrange/Overrange Error can be set in the CoE.

In Legacy Range mode, an Underrange/Overrange event also leads to an Error in the PDO status.