Measurement 0…20 mA

Measurement mode

0…20 mA

Measuring range, nominal

0…20 mA

Measuring range, end value (full scale value)

20 mA

Measuring range, technically usable

0 …21.474 mA

Fuse protection

Internal overload limiting, continuous current resistant

PDO resolution

23 bit (unsigned)

PDO LSB (Extended Range)

2.56 nA

PDO LSB (Legacy Range)

2.384.. nA

Common-mode voltage Vcm

max. +/- 10V

related to -Uv (internal ground)

Basic accuracy: Measuring deviation at 23°C, with averaging

< ±0.01%FSV = ±100 ppmFSV

Offset/Zero Point deviation (at 23°C)

EOffset

< 65 ppmFSV

Gain/scale/amplification deviation (at 23°C)

EGain

< 50 ppm

Non-linearity over the whole measuring range

ELin

< 40 ppmFSV

Repeatability

ERep

< 40 ppmFSV

Noise (without filtering)

ENoise, PtP

< 100 ppmFSV

< 781 [digits]

ENoise, RMS

< 18 ppmFSV

< 141 [digits]

Max. SNR

> 94.9 dB

Noisedensity@1kHz

< 5.09 Measurement 0…20 mA 1:

Noise (with 50Hz FIR filtering)

ENoise, PtP

< 10 ppmFSV

< 78 [digits]

ENoise, RMS

< 2.0 ppmFSV

< 16 [digits]

Max. SNR

> 114.0 dB

Temperature coefficient

TcGain

< 15 ppm/K typ.

TcOffset

< 5 ppmFSV/K typ.

Common-mode rejection ratio (without filtering)

DC: < 3 nA/V typ.

50 Hz: < 5  nA/V typ.

1 kHz: < 80  nA/V typ.

Common-mode rejection ratio (with 50Hz FIR filtering)

DC: < 3 nA/V typ.

50 Hz: < 3 nA/V typ.

1 kHz: < 3 nA/V typ.

Largest short-term deviation during a specified electrical interference test

±0.05%FSV = ±500 ppmFSV typ.

Input impedance ±Input 1

(Internal resistance)

Differential 200 Ω || 11 nF typ.

CommonMode 1 MΩ || 40 nF typ.

Methodology: Resistor against -UV, capacitance against SGND

Input impedance ±Input 2

No usage of this input in this mode

Current measurement range 0…20 mA

Measurement 0…20 mA 2:Fig.35: Representation current measurement range 0…20 mA
Measurement 0…20 mA 3:Fig.34: Frequency response 0…20 mA measurement range, fsampling = 10 kHz, integrated filter 1/2 deactivated