Sample program 1 and 2 (offset/gain)

Download TwinCAT 3 project:

Program link

Program description / function:

The configuration of the minimum permitted input frequency, the order of the Gain and Offset calculations, and the direct writing to the CoE directory ("PAI Scaler Settings" object) can be done in this sample program (see Variable declaration).

The following procedure is foreseen:

  1. Configuration of "bWriteToCoEEnable" = TRUE, i.e. on completion of the calculation of the correction values, they are written to the CoE object "PAI Scaler Settings".
  2. Set the terminal to "Extended Range" (0) via the object "PAI Settings Ch. 1" 0x8000:2E in the CoE directory.
  3. Connect a periodic signal (triangle, sine, square, …) to the terminal within the selected voltage/current range via the PAI Settings object 0x8000:01 (Interface).
  4. Start the program by setting "bEnable" to "TRUE".
  5. The end of the execution is recognizable by the variables "bScaleGainDone" and "bScaleOffsetDone", which are then both TRUE.
  6. If writing is enabled in the CoE ("bWriteToCoEEnable" = TRUE), the values determined should have been written to the object "PAI Scaler Settings" in the CoE directory (see variable "bError").
  7. If 6th was executed, the terminal can be set to "Linear" (1) via the object "PAI Settings Ch. 1" 0x8000:2E in the CoE directory. As a result, the terminal also performs the correction calculation internally (see: "nScaledSampleVal").

Comments:

Alternatively, the TC3 Analytics Library (TF3510) can be used instead of the function block "FB_GET_MIN_MAX". The function block "FB_ALY_MinMaxAvg_1Ch" can also be used for the determination of the min./max. values. The total calculation can then also be modified in this program by using the mean value provided by this function block.

In the case of the ELM350x/ ELM370x terminals , the "PAI Scaler Settings" object is 0x80n6, in addition to which the nOffset and nGain variables can also be directly written without the type conversion (REAL to DINT); scaling of the amplitude correction values with 65536 is also no longer necessary.

Example program 1 and 2 variable declaration:

PROGRAM MAIN
VAR_INPUT
   bEnable               :BOOL; // Start the code (Offset / Gain adjust)
   nPAI_Sample AT%I*     :DINT; // Input samples of the measurement value
END_VAR
VAR
   // Enter your Net-Id here:
   userNetId             :T_AmsNetId := 'a.b.c.d.x.y';
   // Enter EtherCAT device address here:
   nUserSlaveAddr        :UINT := 1002; // Check, if correct
   // Configurations:
   fMinFrequencyIn       :REAL:=1.5; // Hz
   bScalingOrder         :BOOL:=FALSE; // TRUE: Start scale offset first
   bWriteToCoEEnable     :BOOL:=FALSE; // TRUE: Enable writing to CoE
   // ===============================================
   // "Main" State controlling Offset/Gain adjusting:
   nMainCal_State        :BYTE:=0;
   // For CoE Object 0x8005 access:
   fb_coe_write          :FB_EcCoESdoWrite; // FB for writing to CoE
   nSTATE_WRITE_COE      :BYTE := 0;
   nSubIndex             :BYTE;
   nCoEIndexScaler       :WORD := 16#8005; // Use channel 1
   // For ELM3xxx this is 0x8006
   nSubIndScalGain       :BYTE := 16#02;
   nSubIndScalOffs       :BYTE := 16#01;
   nADSErrId             :UDINT; // Copy of ADS-Error ID
   // ===============================================
   fb_get_min_max        :FB_GET_MIN_MAX; // Min/Max values needed
   // Note: you may also use "FB_ALY_MinMaxAvg_1Ch" of TwinCAT analytics)
   // instead; there avg (average values can also be determinated
   // Variables used for offset scaling:
   nSTATE_SCALE_OFFSET   :INT := 0;
   bScaleOffsetStart     :BOOL := FALSE;
   bScaleOffsetDone      :BOOL := FALSE;
   fOffsetDeviationVal   :REAL;
   nOFFSET_MIN_VAL_REF   :WORD := 200;  // Max. limit value for offset
   // Variables used for gain scaling:
   nSTATE_SCALE_GAIN     :INT := 0;
   bScaleGainStart       :BOOL := FALSE;
   bScaleGainDone        :BOOL := FALSE;
   nPRESET_MAX_VAL       :REAL := 3000000; // Target amplitude value
   // ===============================================
   // Variables for evaluating of gain and offset:
   nOffset               :REAL := 0; // Offset value
   nGain                 :REAL := 1; // Gain value
   nScaledSampleVal      :REAL;
   nDINT_Value           :DINT;
   fb_trig_bEnable       :R_TRIG; // Trigger FB for Enable
   bError                :BOOL := FALSE; // Evaluate..
END_VAR

Execution part:

// THIS CODE IS ONLY AN EXAMPLE - YOU HAVE TO CHECK APTITUDE FOR YOUR APPLICATION
// Example program 1 and 2 program code:
// =====================================
// 1. PAI setting of 0x80n0:2E must be "Extended Range" at first
// 2. When writing of scaling values were done, switch to "Linear"

// Calculation of the temporary value (..and use for ScopeView to check)
nScaledSampleVal := nOffset + nGain * DINT_TO_REAL(nPAI_Sample);
// Main-State Procedure:
CASE nMainCal_State OF
   0:
      fb_trig_bEnable(CLK:=(bEnable AND NOT bError));
      IF fb_trig_bEnable.Q THEN // Poll switch or button
         // Initialize temporary offset and gain values:
         nOffset:= 0;
         nGain  := 1;
         bScaleOffsetStart := bScalingOrder;
         bScaleGainStart   := NOT bScalingOrder;

         fb_get_min_max.nMinFreqInput := fMinFrequencyIn;

         nMainCal_State := 10; // Start
      END_IF
   10:
      IF (bScaleGainDone AND NOT bScalingOrder)
        OR (bScaleOffsetDone AND bScalingOrder) THEN
         bScaleOffsetStart := NOT bScalingOrder;
         bScaleGainStart   := bScalingOrder;
         nMainCal_State := nMainCal_State + 10;
      END_IF
   20:
      IF bScaleGainDone AND bScaleOffsetDone THEN
         nMainCal_State :=0; // All done, initalization for next start
      END_IF
END_CASE

// ----- Offset scaling (program 1) -----
IF bScaleOffsetStart THEN
   CASE nSTATE_SCALE_OFFSET OF
   0:
      bScaleOffsetDone := FALSE; // Initialization of confirmation flag
      // Get min/max values within a period of the signal:
      fb_get_min_max(nInputValue:=nScaledSampleVal);
      IF fb_get_min_max.bRESULT THEN // Wait if Limit-Values are valid
         // Min/Max Values valid, continue..
         // calculate current offset deviation:
         fOffsetDeviationVal :=
         (fb_get_min_max.nMaxVal - ABS((fb_get_min_max.nMaxVal-fb_get_min_max.nMinVal)/2));

         // Offset deviation check:
         IF ABS(fOffsetDeviationVal) < nOFFSET_MIN_VAL_REF THEN
            // Deviation in acceptable range - offset scaling done,
            // now write correction value into CoE Object:
            nDINT_Value := REAL_TO_DINT(nOffset);

            // Initiate writing to CoE:
            nSubIndex := nSubIndScalOffs;
            nSTATE_WRITE_COE := 10;
            nSTATE_SCALE_OFFSET := nSTATE_SCALE_OFFSET + 10;
         ELSE
            // Calculate new offset value (new by old with deviation)
            nOffset := nOffset - fOffsetDeviationVal;
         END_IF
      END_IF
   10:
      IF(nSTATE_WRITE_COE = 0) THEN
         // Scaling offset done within CoE for the device
         bScaleOffsetDone := TRUE;
         bScaleOffsetStart := FALSE;
         nSTATE_SCALE_OFFSET := 0;
      END_IF
   END_CASE
END_IF

// ----- Gain scaling (program 2) -----
IF bScaleGainStart THEN
   CASE nSTATE_SCALE_GAIN OF
   0:
      bScaleGainDone := FALSE; // Initialization of confirmation flag
      // Get min/max values within a period of the signal:
      fb_get_min_max(nInputValue:=DINT_TO_REAL(nPAI_Sample));
      IF fb_get_min_max.bRESULT THEN // Wait if Limit-Values are valid

         // Calculate Gain 
         nGain := nPRESET_MAX_VAL/ABS((fb_get_min_max.nMaxVal-fb_get_min_max.nMinVal)/2);
         // ..shift gain value by 16 Bit left and convert to DINT:
         nDINT_Value := REAL_TO_DINT(65536 * nGain);

         //Due to 'output = gain * input + offset', the offset have to be adapted:
         nOffset := nOffset * nGain;

          // Initiate writing to CoE:
         nSubIndex := nSubIndScalGain;
         nSTATE_WRITE_COE := 10;
         nSTATE_SCALE_GAIN := nSTATE_SCALE_GAIN + 10;
      END_IF
   10:
      IF(nSTATE_WRITE_COE = 0) THEN
         IF NOT (nOffset = 0) THEN
            // (bScalingOrder is TRUE)
            nDINT_Value := REAL_TO_DINT(nOffset);
            // Initiate writing to CoE (again):
            nSubIndex := nSubIndScalOffs;
            nSTATE_WRITE_COE := 10;
         END_IF

         nSTATE_SCALE_GAIN := nSTATE_SCALE_GAIN + 10;
      END_IF   
   20:
      IF(nSTATE_WRITE_COE = 0) THEN        
         // Scaling gain done within CoE for the device
         bScaleGainStart := FALSE;
         bScaleGainDone := TRUE;
         nSTATE_SCALE_GAIN := 0; // Set initial state
      END_IF
   END_CASE
END_IF

IF (nSTATE_WRITE_COE > 0) THEN
   IF bWriteToCoEEnable THEN
      CASE nSTATE_WRITE_COE OF
      10:
         // Prepare CoE write access
         fb_coe_write(
            sNetId:=     userNetId,
            nSlaveAddr:= nUserSlaveAddr,
            nIndex:=     nCoEIndexScaler,
            bExecute:=   FALSE,
            tTimeout:=   T#1S
         ); 
         nSTATE_WRITE_COE := nSTATE_WRITE_COE + 10;
      20:
         // Write nDINT_Value to CoE Index "Scaler":
         fb_coe_write(
         nSubIndex:= nSubIndex,
         pSrcBuf:= ADR(nDINT_Value),
         cbBufLen:= SIZEOF(nDINT_Value),
         bExecute:= TRUE
         );
         nSTATE_WRITE_COE := nSTATE_WRITE_COE + 10;
      30:
         fb_coe_write();
         IF NOT fb_coe_write.bBusy THEN
            nSTATE_WRITE_COE := 0;
         END_IF
      END_CASE
   ELSE
      nSTATE_WRITE_COE := 0;
   END_IF
END_IF

IF(fb_coe_write.bError) AND NOT bError THEN
   bError := TRUE;
   nADSErrId := fb_coe_write.nErrId;
   // CoE write acccess error occured: reset all
   nSTATE_WRITE_COE := nMainCal_State := 0;
   bScaleOffsetDone := bScaleOffsetStart := FALSE;
   bScaleGainDone   := bScaleGainStart   := FALSE;
END_IF