0x9000 PAI Internal Data Ch.1
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
9000:0 | PAI Internal Data Ch.1 |
| UINT8 | RO | 0x12 (18dec) 0x13 (19dec) 1) 0x15 (21dec) 2) |
9000:01 | Temperature Value | Temperature value of the channel | INT16 | RO | 0x0000 (0dec) |
9000:02 | ADC Raw Value | ADC Raw Value | INT32 | RO | 0x00000000 (0dec) |
9000:03 | Calibration Value | Value after calibration | INT32 | RO | 0x00000000 (0dec) |
9000:04 | Resistor Value | Value after resistance calculation | INT32 | RO | 0x00000000 (0dec) |
9000:05 | RTD Element Value | Value after RTD element calculation | INT32 | RO | 0x00000000 (0dec) |
9000:06 | Actual Negative Peak Hold | Current absolute minimum value | INT32 | RO | 0x00000000 (0dec) |
9000:07 | Actual Positive Peak Hold | Current absolute maximum value | INT32 | RO | 0x00000000 (0dec) |
9000:08 | Previous Negative Peak Hold | Absolute minimum value up to last rising edge of "Peak Hold Reset" | INT32 | RO | 0x00000000 (0dec) |
9000:09 | Previous Positive Peak Hold | Absolute maximum value up to last rising edge of "Peak Hold Reset" | INT32 | RO | 0x00000000 (0dec) |
9000:0A | Filter 1 Value | Value after filter 1 | INT32 | RO | 0x00000000 (0dec) |
9000:0B | Filter 2 Value | Value after filter 2 | INT32 | RO | 0x00000000 (0dec) |
9000:0C | True RMS Value | Value after "True RMS" calculation | INT32 | RO | 0x00000000 (0dec) |
9000:0D | Extended Functions Value | Value after advanced (optional) function | INT32 | RO | 0x00000000 (0dec) |
9000:0E | Integrator/Differentiator Value | Value after integration or differentiation | INT32 | RO | 0x00000000 (0dec) |
9000:0F | Scaler Value | Value after scaling | INT32 | RO | 0x00000000 (0dec) |
9000:10 | Limiter Value | Value after limitation | INT32 | RO | 0x00000000 (0dec) |
9000:11 | Overload Time | Absolute time during overload | UINT32 | RO | 0x00000000 (0dec) |
9000:12 | Saturation Time | Absolute time during saturation Its accumulated response time is displayed here informatively. | UINT32 | RO | 0x00000000 (0dec) |
9000:13 | Effective Sample Rate | Effective sampling frequency 1) | UINT32 | RO | Online calculated |
9000:14 | Vendor Calibration Counter | Writing counter for vendor calibration data 2) | UINT16 | RO | 0x0000 (0dec) |
9000:15 | User Calibration Counter | Writing counter for user calibration data 2) | UINT16 | RO | 0x0000 (0dec) |
1) available from revision -0019
2) available from revision -0020