0x8000 PAI Settings Ch.1
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
8000:0 |
PAI Settings Ch.1 |
|
UINT8 |
RO |
0x34 (52dec) 0x41 (65dec) 2) |
|
8000:01 |
Interface |
Selection of the measurement configuration: |
UINT16 |
RW |
0x0000 (0dec) |
|
8000:02 |
SG Voltage |
Selection of the SG voltage: |
UINT16 |
RW |
0x0000 (0dec) |
|
8000:04 |
Wire Break Detection |
Broken wire detection |
BOOLEAN |
RW |
0x00 (FALSE) |
|
8000:13 |
Wire Resistance Compensation 640 µΩ/ Step |
Compensation of the wire resistance with resolution 640 µΩ/ step (only in 2-wire mode, "R/RTD 2-wire" possible) |
UINT16 |
RW |
0x0000 (0dec) |
|
8000:14 |
RTD Element |
Selection of the RTD element: |
UINT16 |
RW |
0x0000 (0dec) |
|
8000:16 |
Filter 1 |
Options for filter 1: |
UINT16 |
RW |
0x0000 (0dec) |
|
8000:17 |
Average Filter 1 No of Samples |
Number of samples for user-defined Average Filter 1 |
UINT16 |
RW |
0x0001 (1dec) |
|
8000:18 |
Decimation Factor |
Factor for individual sampling rate (min. 1) |
UINT16 |
RW |
0x0001 (1dec) |
|
8000:19 |
Filter 2 |
Options for filter 2: |
UINT16 |
RW |
0x0000 (0dec) |
|
8000:1A |
Average Filter 2 No of Samples |
Number of samples for user-defined Average Filter 2 |
UINT16 |
RW |
0x0001 (1dec) |
|
8000:1B |
True RMS No. of Samples |
Number of samples for “True RMS“ calculation (min. 1, max. 1000); |
UINT16 |
RW |
0x00C2 (200dec) |
|
8000:1C |
Enable True RMS |
Activation of "True RMS" calculation |
BOOLEAN |
RW |
0x00 (FALSE) |
|
8000:2B |
Extended Functions |
Options for future functions /settings |
UINT16 |
RW |
0x0000 (0dec) |
|
8000:2C |
Integrator/Differentiator |
Options: |
UINT16 |
RW |
0x0000 (0dec) |
|
8000:2D |
Differentiator Samples Delta |
Distance of samples for the differentiation |
UINT16 |
RW |
0x0001 (1dec) |
|
8000:2E |
Scaler |
Scaling (enum): |
UINT16 |
RW |
0x0000 (0dec) |
|
8000:30 |
Low Limiter |
Smallest PDO output value |
INT32 |
RW |
0x80000000 (-2147483648dec) |
|
8000:31 |
High Limiter |
Largest PDO output value |
INT32 |
RW |
0x7FFFFFFF (2147483647dec) |
|
8000:32 |
Low Range Error |
Lowest limit at which the error bit and the error LED are set |
INT32 |
RW |
0xFF800000 |
|
8000:33 |
High Range Error |
Highest limit at which the error bit and the error LED are set |
INT32 |
RW |
0x007FFFFF |
|
8000:34 |
Timestamp Correction |
Value for correcting StartNextLatchTime (timestamp of the first sample) |
INT32 |
RW |
0xFFFB6C20 |
|
8000:40 |
Filter 1 Type Info |
Filter 1 type information 2) |
STRING |
RW |
N/A |
|
8000:41 |
Filter 2 Type Info |
Filter 2 type information 2) |
STRING |
RW |
N/A |
1) Functionality is only available from FW03
2) Functionality is only available from FW11, revision -0022