0x6000 PAI Status Ch.1
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
---|---|---|---|---|---|
6000:0 |
PAI Status Ch.1 |
|
UINT8 |
RO |
0x0F (15dec) |
6000:01 |
No of Samples |
Number of valid samples within the PDO samples |
UINT8 |
RO |
0x00 (0dec) |
6000:09 |
Error |
TRUE: General error |
BOOLEAN |
RO |
0x00 (0dec) |
6000:0A |
Underrange |
TRUE: Measurement event underflow |
BOOLEAN |
RO |
0x00 (0dec) |
6000:0B |
Overrange |
TRUE: Measurement event overflow |
BOOLEAN |
RO |
0x00 (0dec) |
6000:0D |
Diag |
TRUE: New diagnostic message available |
BOOLEAN |
RO |
0x00 (0dec) |
6000:0E |
TxPDO State |
TRUE: data invalid |
BOOLEAN |
RO |
0x00 (0dec) |
6000:0F |
Input cycle counter |
Incremented by one when values have changed |
BIT2 |
RO |
0x00 (0dec) |