Configuration data (vendor-specific)
Index 800F* AI Vendor data Ch.1
Index (hex) | Name | Meaning | Data type | Flags | Default | |
|---|---|---|---|---|---|---|
800F:0 | AI Vendor data Ch.1 | Maximum subindex | UINT8 | RO | 0x09 (9dec) | |
800F:01 | Calibration offset | Offset (vendor calibration) | INT32 | RW | 0x00000000 (0dec) | |
800F:02 | EL3602: | Calibration gain | Gain + 10 V range (vendor calibration) | UINT32 | RW | 0x00944000 (9715712dec) |
EL3602-0010: | Calibration gain pos | Gain pos. (vendor calibration) | ||||
EL3612: | Calibration gain 1 | Gain 1 (vendor calibration) | ||||
800F:03 | EL3602: | Calibration gain | Gain - 10 V range (vendor calibration) | UINT32 | RW | 0x00944000 (9715712dec) |
EL3602-0010: | Calibration gain neg. | Gain neg. (vendor calibration) | ||||
EL3612: | Calibration gain 2 | Gain 2 (vendor calibration) | 0x00000000 | |||
800F:04 | EL3602: | Calibration gain | Gain + 5 V range (vendor calibration) | UINT32 | RW | 0x00944000 (9715712dec) |
EL3612: | Calibration gain 3 | Gain 3 (vendor calibration) | ||||
800F:05 | EL3602: | Calibration gain | Gain - 5 V range (vendor calibration) | UINT32 | RW | 0x00944000 (9715712dec) |
EL3612: | Calibration gain 4 | Gain 4 (vendor calibration) | 0x00000000 | |||
800F:06 | EL3602: | Calibration gain | Gain + 2.5 V range (vendor calibration) | UINT32 | RW | 0x00944000 (9715712dec) |
EL3612: | Calibration gain 5 | Gain 5 (vendor calibration) | ||||
800F:07 | EL3602: | Calibration gain | Gain – 2.5 V range (vendor calibration) | UINT32 | RW | 0x00944000 (9715712dec) |
EL3612: | Calibration gain 6 | Gain 6 (vendor calibration) | ||||
800F:08 | EL3602: | Calibration gain | Gain + 1.25 V range (vendor calibration) | UINT32 | RW | 0x00944000 (9715712dec) |
EL3612: | Calibration gain 7 | Gain7 (vendor calibration) | ||||
800F:09 | EL3602: | Calibration gain | Gain – 1.25 V range (vendor calibration) | UINT32 | RW | 0x00944000 (9715712dec) |
EL3612: | Calibration gain 8 | Gain 8 (vendor calibration) | ||||
*) not valid for EL3621-0020
Index 800F AI Vendor data (EL3621-0020 only)
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
800F:0 | AI Vendor data Ch.1 | Maximum subindex | UINT8 | RO | 0x02 (2dec) |
800F:01 | Calibration offset | Offset (vendor calibration) | INT32 | RW | 0x00000000 (0dec) |
800F:02 | Calibration gain | Gain (vendor calibration) | UINT32 | RW | 0x00944000 (9715712dec) |
Index 801F*** AI Vendor data Ch.2
Index (hex) | Name | Meaning | Data type | Flags | Default | |
|---|---|---|---|---|---|---|
801F:0 | AI Vendor data Ch.2 | Maximum subindex | UINT8 | RO | 0x09 (9dec) | |
801F:01 | Calibration offset | Offset (vendor calibration) | INT32 | RW | 0x00000000 (0dec) | |
801F:02 | EL3602: | Calibration gain | Gain + 10 V range (vendor calibration) | UINT32 | RW | 0x00944000 (9715712dec) |
EL3602-0010: | Calibration gain pos. | Gain pos. (vendor calibration) | ||||
EL3612: | Calibration gain 1 | Gain 1 (vendor calibration) | ||||
801F:03 | EL3602: | Calibration gain | Gain – 10 V range (vendor calibration) | UINT32 | RW | 0x00944000 (9715712dec) |
EL3602-0010: | Calibration gain neg. | Gain neg. (vendor calibration) | ||||
EL3612: | Calibration gain 2 | Gain 2 (vendor calibration) | 0x00000000 | |||
801F:04 | EL3602: | Calibration gain | Gain + 5 V range (vendor calibration) | UINT32 | RW | 0x00944000 (9715712dec) |
EL3612: | Calibration gain 3 | Gain 3 (vendor calibration) | ||||
801F:05 | EL3602: | Calibration gain | Gain – 5 V range (vendor calibration) | UINT32 | RW | 0x00944000 (9715712dec) |
EL3612: | Calibration gain 4 | Gain 4 (vendor calibration) | 0x00000000 | |||
801F:06 | EL3602: | Calibration gain | Gain + 2.5 V range (vendor calibration) | UINT32 | RW | 0x00944000 (9715712dec) |
EL3612: | Calibration gain 5 | Gain 5 (vendor calibration) | ||||
801F:07 | EL3602: | Calibration gain | Gain - 2.5 V range (vendor calibration) | UINT32 | RW | 0x00944000 (9715712dec) |
EL3612: | Calibration gain 6 | Gain 6 (vendor calibration) | ||||
801F:08 | EL3602: | Calibration gain | Gain + 1.25 V range (vendor calibration) | UINT32 | RW | 0x00944000 (9715712dec) |
EL3612: | Calibration gain 7 | Gain7 (vendor calibration) | ||||
801F:09 | EL3602: | Calibration gain | Gain – 1.25 V range (vendor calibration) | UINT32 | RW | 0x00944000 (9715712dec) |
EL3612: | Calibration gain 8 | Gain 8 (vendor calibration) | ||||
***) EL3602 (EL3602-xxxx), EL3612 (EL3612-xxxx) only