Information and diagnostic data

Index 80nE SAI Internal Data (for Ch.1 (n=0); Ch.2 (n=1)

Index (hex)

Name

Meaning

Data type

Flags

Default

800E:0

SAI Internal Data

Maximum subindex

UINT8

RO

0x03 (3dec)

80nE:01

Raw value

ADC raw value

UINT32

RO

0x00000000 (0dec)

80nE:03

Sampling Time

Duration of the last conversion in ms

UINT16

RO

0x0000 (0dec)

Index F000 Modular device profile

Index (hex)

Name

Meaning

Data type

Flags

Default

F000:0

Modular device profile

General information for the modular device profile

UINT8

RO

0x02 (2dec)

F000:01

Module index distance

Index distance of the objects of the individual channels

UINT16

RO

0x0010 (16dec)

F000:02

Maximum number of modules

Number of channels

UINT16

RO

0x0002 (2dec)

Index F008 Code word

Index (hex)

Name

Meaning

Data type

Flags

Default

F008:0

Code word

currently reserved

UINT32

RW

0x00000000 (0dec)

Index F010Module list

Index (hex)

Name

Meaning

Data type

Flags

Default

F010:0

Module list

Module list

UINT8

RO

0x02 (2dec)

F010:01

Subindex 001

Profile of the first module

UINT32

RO

0x168 (360dec)

F000:02

Subindex 002

Profile of the second module

UINT16

RO

0x168 (360dec)