Input data

Index 60n0 DPM Channel (for Ch.1 n = 0; Ch.2 n = 1; Ch.3 n = 2; Ch.4 n = 3; Ch.5 n = 4; Ch.6 n = 5)

Index (hex)

Name

Meaning

Data type

Flags

Default

60n0:0

DPM Channel

Max. subindex

UINT8

RO

0x15 (21dec)

60n0:01

Overcurrent

Maximum measurable current is exceeded.

BOOLEAN

RO

0x00 (0dec)

60n0:02

Inaccurate Current

The measured current value is outside the current limits entered in CoE object 0x80n2

BOOLEAN

RO

0x00 (0dec)

60n0:03

Current Guard Warning

The measured current value is outside the warning limits entered in the CoE objects 0x80n2:06 and 0x80n2:07

BOOLEAN

RO

0x00 (0dec)

60n0:04

Current Guard Error

The measured current value is outside the error limits entered in the CoE objects 0x80n2:05 and 0x80n2:08

BOOLEAN

RO

0x00 (0dec)

60n0:05

Apparent Power Guard Warning

The value for the apparent power is outside the warning limits entered in the CoE objects 0x80n2:0A and 0x80n2:0B

BOOLEAN

RO

0x00 (0dec)

60n0:06

Apparent Power Guard Error

The value for the apparent power is outside the error limits for the current entered in the CoE objects 0x80n2:09 and 0x80n2:0C

BOOLEAN

RO

0x00 (0dec)

60n0:07

Active Power Guard Warning

The value for the active power is outside the warning limits entered in the CoE objects 0x80n2:0E and 0x80n2:0F

BOOLEAN

RO

0x00 (0dec)

60n0:08

Active Power Guard Error

The value for the active power is outside the error limits for the current entered in the CoE objects 0x80n2:0D and 0x80n2:10

BOOLEAN

RO

0x00 (0dec)

60n0:09

Reactive Power Guard Warning

The value for the reactive power is outside the warning limits entered in the CoE objects 0x80n2:12 and 0x80n2:13

BOOLEAN

RO

0x00 (0dec)

60n0:0A

Reactive Power Guard Error

The value for the reactive power is outside the error limits for the current entered in the CoE objects 0x80n2:11 and 0x80n2:14

BOOLEAN

RO

0x00 (0dec)

60n0:0B

DPM Inaccurate

Bit indicates that the calculated DPM values (e.g. power) may be inaccurate due to insufficient current input signals (e.g. too low amplitude).

BOOLEAN

RO

0x00 (0dec)

60n0:0C

DPM Timeout

Bit indicates that the transmitted DPM voltage values arrive too late in the current-measuring terminal to ensure optimum power calculation.

BOOLEAN

RO

0x00 (0dec)

60n0:10

TxPDO Toggle

The TxPDO toggle is toggled by the slave when the data of the associated TxPDO is updated.

BOOLEAN

RO

0x00 (0dec)

60n0:11

Current

Current measured current value

REAL32

RO

0.000000 (0.000000e+000)

60n0:12

Active Power

Current measured active power

REAL32

RO

0.000000 (0.000000e+000)

60n0:13

Apparent Power

Current measured apparent power

REAL32

RO

0.000000 (0.000000e+000)

60n0:14

Reactive Power Fundamental

Recorded reactive power fundamental

REAL32

RO

0.000000 (0.000000e+000)

60n0:15

Active Energy

Current measured active energy

REAL32

RO

0.000000 (0.000000e+000)

Index 60n1 DPM Channel Current (for Ch.1 n = 0; Ch.2 n = 1; Ch.3 n = 2; Ch.4 n = 3; Ch.5 n = 4; Ch.6 n = 5)

Index (hex)

Name

Meaning

Data type

Flags

Default

60n1:0

DPM Channel Current

Max. Subindex

UINT8

RO

0x11 (17dec)

60n1:01

Overcurrent

Maximum measurable current is exceeded.

BOOLEAN

RO

0x00 (0dec)

60n1:02

Inaccurate Current

The measured current value is outside the current limits entered in CoE object 0x80n2

BOOLEAN

RO

0x00 (0dec)

60n1:03

Current Guard Warning

The measured current value is outside the warning limits entered in the CoE objects 0x80n2:06 and 0x80n2:07

BOOLEAN

RO

0x00 (0dec)

60n1:04

Current Guard Error

The measured current value is outside the error limits entered in the CoE objects 0x80n2:05 and 0x80n2:08

BOOLEAN

RO

0x00 (0dec)

60n1:10

TxPDO Toggle

The TxPDO toggle is toggled by the slave when the data of the associated TxPDO is updated.

BOOLEAN

RO

0x00 (0dec)

60n1:11

Current

Current measured current value

REAL32

RO

0.000000 (0.000000e+000)

Index 606A DPM Variant Value In

Index (hex)

Name

Meaning

Data type

Flags

Default

606A:0

DPM Variant Value In

Max. subindex

UINT8

RO

0x18 (24dec)

606A:10

TxPDO Toggle

The TxPDO toggle is toggled by the slave when the data of the associated TxPDO is updated.

BOOLEAN

RO

0x00 (0dec)

606A:11

Index 1 REAL

Acknowledge for variable output value 1

UINT16

RO

0x0000 (0dec)

606A:12

Value 1 REAL

Variable output value channel 1

REAL32

RO

0.000000 (0.000000e+000)

606A:13

Index 2 REAL

Acknowledge for variable output value 2

UINT16

RO

0x0000 (0dec)

606A:14

Value 2 REAL

Variable output value channel 2

REAL32

RO

0.000000 (0.000000e+000)

606A:15

Index 3 REAL

Acknowledge for variable output value 3

UINT16

RO

0x0000 (0dec)

606A:16

Value 3 REAL

Variable output value channel 3

REAL32

RO

0.000000 (0.000000e+000)

606A:17

Index 4 ULINT

Acknowledge for variable output value 4

UINT16

RO

0x0000 (0dec)

606A:18

Value 4 ULINT

Variable output value channel 4

UINT64

RO