Input data

Index 60n0 PMX status (n = 0, 1, 2)

Index (hex)

Name

Meaning

Data type

Flags

Default

60n0:0

PMX Status

Max. subindex

UINT8

RO

0x10 (16dec)

60n0:01

Voltage Sign Bit

Indicates the sign of the current sine wave voltage:

1 = U > 0V
0 = U < 0V

BOOLEAN

RO

0x00 (0dec)

60n0:02

Overvoltage

Maximum measurable voltage is exceeded.

BOOLEAN

RO

0x00 (0dec)

60n0:03

Overcurrent

Maximum measurable current is exceeded.

BOOLEAN

RO

0x00 (0dec)

60n0:04

Inaccurate Voltage

The measured voltage value is smaller than the value entered in CoE object "F800:15 Inaccurate Threshold Voltage".

BOOLEAN

RO

0x00 (0dec)

60n0:05

Inaccurate Current

The measured current value is smaller than the value entered in CoE object "F800:16 Inaccurate Threshold Current".

BOOLEAN

RO

0x00 (0dec)

60n0:06

Voltage Guard Warning

A warning limit of the voltage monitor has been breached.

BOOLEAN

RO

0x00 (0dec)

60n0:07

Voltage Guard Error

An error limit of the voltage monitor has been breached.

BOOLEAN

RO

0x00 (0dec)

6000:10

TxPDO Toggle

The TxPDO toggle is toggled by the slave when the data of the associated TxPDO is updated.

BOOLEAN

RO

0x00 (0dec)

Index 60n1 PMX Basic (n = 0, 1, 2)

Index (hex)

Name

Meaning

Data type

Flags

Default

60n1:0

PMX Basic

 Max. subindex

UINT8

RO

0x12 (18dec)

60n1:11

Voltage

 RMS value of the voltage in V

REAL32

RO

0.000000 (0.000000e+000)

60n1:12

Current

 RMS value of the current in A

REAL32

RO

0.000000 (0.000000e+000)

Index 60n2 PMX Power (n = 0, 1, 2)

Index (hex)

Name

Meaning

Data type

Flags

Default

60n2:0

PMX Power

 Max. subindex

UINT8

RO

0x14 (20dec)

60n2:11

Active Power

 Active power in W

REAL32

RO

0.000000 (0.000000e+000)

60n2:12

Apparent Power

 Apparent power in VA

REAL32

RO

0.000000 (0.000000e+000)

60n2:13

Reactive Power

 Reactive power in var

REAL32

RO

0.000000 (0.000000e+000)

60n2:14

Power Factor

 Power factor

REAL32

RO

0.000000 (0.000000e+000)

Index 60n3 PMX Power Fundamental (n = 0, 1, 2)

Index (hex)

Name

Meaning

Data type

Flags

Default

60n3:0

PMX Power Fundamental

 Max. subindex

UINT8

RO

0x13 (19dec)

60n3:11

Active Power Fund

 Active power fundamental in W

REAL32

RO

0.000000 (0.000000e+000)

60n3:12

Apparent Power Fund

 Apparent power fundamental in VA

REAL32

RO

0.000000 (0.000000e+000)

60n3:13

Reactive Power Fund

 Reactive power fundamental in var

REAL32

RO

0.000000 (0.000000e+000)

Index 60n4 PMX Energy (n = 0, 1, 2)

Index (hex)

Name

Meaning

Data type

Flags

Default

60n4:0

PMX Energy

Max. subindex

UINT8

RO

0x13 (19dec)

60n4:11

Active Energy

Active energy in mWh

INT64

RO

 

60n4:12

Apparent Energy

Apparent energy in mVAh

INT64

RO

 

60n4:13

Reactive Energy

Reactive energy in mvarh

INT64

RO

 

Index 60n5 PMX Energy (n = 0, 1, 2)

Index (hex)

Name

Meaning

Data type

Flags

Default

60n5:0

PMX Energy Fundamental

Max. subindex

UINT8

RO

0x13 (19dec)

60n5:11

Active Energy Fund

Active energy fundamental in mWh

INT64

RO

 

60n5:12

Apparent Energy Fund

Apparent energy fundamental in mVAh

INT64

RO

 

60n5:13

Reactive Energy Fund

Reactive energy fundamental in mvarh

INT64

RO

 

Index 60n6 PMX Timing (n = 0, 1, 2)

Index (hex)

Name

Meaning

Data type

Flags

Default

60n6:0

PMX Timing

Max Subindex

UINT8

RO

0x12 (18dec)

60n6:12

Voltage Last Zero Crossing

Last detected voltage zero crossing as distributed clock time

UINT64

RO

 

60n6:12

Current Last Zero Crossing

Last detected current zero crossing as distributed clock time

UINT64

RO

 

Index 60n7 PMX Advanced (n = 0, 1, 2)

Index (hex)

Name

Meaning

Data type

Flags

Default

60n7:0

PMX Advanced

Max. subindex

UINT8

RO

0x14 (20dec)

60n7:10

TxPDO Toggle

The TxPDO toggle is toggled by the slave when the data of the associated TxPDO is updated.

BOOLEAN

RO

0x00 (0dec)

60n7:11

Voltage Total Harmonic Distortion

"Total Harmonic Distortion" is the distortion factor of the voltage. It indicates the ratio of the harmonic components of an oscillation relative to its fundamental in %.

REAL32

RO

0.000000 (0.000000e+000)

60n7:12

Current Distortion Factor

The "Current Distortion Factor" is also referred to as TDD (Total Demand Distortion). It indicates the ratio between the current harmonics and the maximum current (EL3443: 1 A and EL3443-0010: 5 A, EL3453: 100 mA/1 A/5 A). Specified in % of the maximum current.

REAL32

RO

0.000000 (0.000000e+000)

60n7:13

Current Total Harmonic Distortion

"Total Harmonic Distortion" is the distortion factor of the current. It indicates the ratio of the harmonic components of an oscillation relative to its fundamental in %.

REAL32

RO

0.000000 (0.000000e+000)

60n7:14

Cos phi

Phase angle of the fundamental wave in degrees

REAL32

RO

0.000000 (0.000000e+000)

Index 60n8 PMX Statistic Voltage (n = 0, 1, 2)

Index (hex)

Name

Meaning

Data type

Flags

Default

60n8:0

PMX Statistic Voltage

Max. subindex

UINT8

RO

0x13 (19dec)

60n8:11

Voltage Peak

Peak value of the instantaneous voltage in the last interval in V

REAL32

RO

0.000000 (0.000000e+000)

60n8:12

Voltage RMS Minimum

Minimum RMS value of the voltage in the last interval in V

REAL32

RO

0.000000 (0.000000e+000)

60n8:13

Voltage RMS Maximum

Maximum RMS value of the voltage in the last interval in V

REAL32

RO

0.000000 (0.000000e+000)

Index 60n9 PMX Statistic Current (n = 0, 1, 2)

Index (hex)

Name

Meaning

Data type

Flags

Default

60n9:0

PMX Statistic Current

Max. subindex

UINT8

RO

0x13 (19dec)

60n9:11

Current Peak

Peak value of the instantaneous current in the last interval in A

REAL32

RO

0.000000 (0.000000e+000)

60n9:12

Current RMS Minimum

Minimum RMS value of the current in the last interval in A

REAL32

RO

0.000000 (0.000000e+000)

60n9:13

Current RMS Maximum

Maximum RMS value of the current in the last interval in A

REAL32

RO

0.000000 (0.000000e+000)

Index 60nA PMX Statistic Power (n = 0, 1, 2)

Index (hex)

Name

Meaning

Data type

Flags

Default

60nA:0

PMX Statistic Power

Max. subindex

UINT8

RO

0x19 (25dec)

60nA:11

Active Power Avg

Average active power in the last interval in W

REAL32

RO

0.000000 (0.000000e+000)

60nA:12

Active Power Min

Minimum active power in the last interval in W

REAL32

RO

0.000000 (0.000000e+000)

60nA:13

Active Power Max

Maximum active power in the last interval in W

REAL32

RO

0.000000 (0.000000e+000)

60nA:14

Apparent Power Avg

Average apparent power in the last interval in VA

REAL32

RO

0.000000 (0.000000e+000)

60nA:15

Apparent Power Max

Maximum apparent power in the last interval in VA

REAL32

RO

0.000000 (0.000000e+000)

60nA:16

Reactive Power Avg

Average reactive power average in the last interval in var

REAL32

RO

0.000000 (0.000000e+000)

60nA:17

Reactive Power Min

Minimum reactive power in the last interval in var

REAL32

RO

0.000000 (0.000000e+000)

60nA:18

Reactive Power Max

Maximum reactive power in the last interval in var

REAL32

RO

0.000000 (0.000000e+000)

60nA:19

Apparent Power Min

Minimum apparent power in the last interval in VA

REAL32

RO

0.000000 (0.000000e+000)

Index 60nB PMX Classic (n = 0, 1, 2)

Index (hex)

Name

Meaning

Data type

Flags

Default

600B:0

PMX Classic

Max. subindex

UINT8

RO

0x16 (22dec)

600B:10

TxPDO Toggle

The TxPDO toggle is toggled by the slave when the data of the associated TxPDO is updated.

BOOLEAN

RO

0x00 (0dec)

600B:11

Voltage

RMS value of the voltage in 0.001 V

INT32

RO

0x00000000 (0dec)

600B:12

Current

RMS value of the current in 0.0001 A

INT32

RO

0x00000000 (0dec)

600B:13

Frequency

Frequency of the fundamental in 0.001 Hz

INT32

RO

0x00000000 (0dec)

600B:14

Active Power

Active power in 0.001 W

INT32

RO

0x00000000 (0dec)

600B:15

Apparent Power

Apparent power in 0.001 VA

INT32

RO

0x00000000 (0dec)

600B:16

Reactive Power

Reactive power in 0.001 var

INT32

RO

0x00000000 (0dec)

Index F600 PMX Total Status

Index (hex)

Name

Meaning

Data type

Flags

Default

F600:0

PMX Total Status

Max. subindex

UINT8

RO

0x11 (17dec)

F600:01

System State

Overall system state (as a logical disjunction of voltage guard errors, phase sequence, overvoltage, overcurrent and frequency guard errors)

BOOLEAN

RO

0x00 (0dec)

F600:02

Grid Direction

Phase sequence L1 - L2 - L3 correctly detected (with clockwise 3-phase mains)

BOOLEAN

RO

0x00 (0dec)

F600:03

Frequency Guard Warning

A warning limit of the frequency monitor has been breached.

BOOLEAN

RO

0x00 (0dec)

F600:04

Frequency Guard Error

An error limit of the frequency monitor has been breached.

BOOLEAN

RO

0x00 (0dec)

F600:05

Neutral Current Guard Warning

A warning limit of the neutral conductor current monitor has been breached.

BOOLEAN

RO

0x00 (0dec)

F600:06

Neutral Current Guard Error

An error limit of the neutral conductor current monitor has been breached.

BOOLEAN

RO

0x00 (0dec)

F600:07

Active Power Guard Warning

A warning limit of the active power monitor has been breached.

BOOLEAN

RO

0x00 (0dec)

F600:08

Active Power Guard Error

An error limit of the active power monitor has been breached.

BOOLEAN

RO

0x00 (0dec)

F600:09

Apparent Power Guard Warning

A warning limit of the apparent power monitor has been breached.

BOOLEAN

RO

0x00 (0dec)

F600:0A

Apparent Power Guard Error

An error limit of the apparent power monitor has been breached.

BOOLEAN

RO

0x00 (0dec)

F600:0B

Power Quality Guard Warning

A warning limit of the PQF monitor has been breached.

BOOLEAN

RO

0x00 (0dec)

F600:0C

Power Quality Guard Error

An error limit of the PQF monitor has been breached.

BOOLEAN

RO

0x00 (0dec)

F600:0F

TxPDO State

TRUE for general error

BOOLEAN

RO

0x00 (0dec)

F600:10

TxPDO Toggle

The TxPDO toggle is toggled by the slave when the data of the associated TxPDO is updated.

BOOLEAN

RO

0x00 (0dec)

F600:11

Power Quality Factor

Analog value of the voltage quality between 1.0 and 0 (see basic function principles - Power Quality Factor)

REAL32

RO

0.000000 (0.000000e+000)

Index F601 PMX Total Basic

Index (hex)

Name

Meaning

Data type

Flags

Default

F601:0

PMX Total Basic

Max. subindex

UINT8

RO

0x13 (19dec)

F601:11

Frequency

Frequency in Hz

REAL32

RO

0.000000 (0.000000e+000)

F601:12

Power Factor

Power factor

REAL32

RO

0.000000 (0.000000e+000)

F601:14

Calculated Error Current

Calculated error current (I_L1 + I_L2 + I_L3 + I_N + I_Err = 0) in A

REAL32

RO

0.000000 (0.000000e+000)

F601:15

Neutral line Current

Measured RMS value of the neutral conductor current in A

REAL32

RO

0.000000 (0.000000e+000)

F601:16

ROCOF

Rate of change of frequency (ROCOF or df/dt) in Hz/s

REAL32

RO

0.000000 (0.000000e+000)

Index F602 PMX Total Advanced

Index (hex)

Name

Meaning

Data type

Flags

Default

F602:0

PMX Total Advanced

Max. subindex

UINT8

RO

0x14 (20dec)

F602:01

Unbalance Guard Warning

A warning limit of the unbalance monitor has been breached.

BOOLEAN

RO

0x00 (0dec)

F602:02

Unbalance Guard Error

An error limit of the unbalance monitor has been breached.

BOOLEAN

RO

0x00 (0dec)

F602:10

TxPDO Toggle

The TxPDO toggle is toggled by the slave when the data of the associated TxPDO is updated.

BOOLEAN

RO

0x00 (0dec)

F602:11

Max Voltage Harmonic Distortion

Maximum distortion factor of all three phase voltages in %

REAL32

RO

0.000000 (0.000000e+000)

F602:12

Max Current Harmonic Distortion

Maximum distortion factor of all three phase currents in %

REAL32

RO

0.000000 (0.000000e+000)

F602:13

Max Current Distortion Factor

Maximum "Total Demand Distortion" value of all three phases in %

REAL32

RO

0.000000 (0.000000e+000)

F602:14

Voltage Unbalance

Ratio between negative and positive voltage system in %

REAL32

RO

0.000000 (0.000000e+000)

Index F603 PMX Total Active

Index (hex)

Name

Meaning

Data type

Flags

Default

F603:0

PMX Total Active

Max. subindex

UINT8

RO

0x14 (20dec)

F603:11

Active Power

Active power in W

REAL32

RO

0.000000 (0.000000e+000)

F603:12

Active Energy

Recorded active energy in mWh

INT64

RO

 

F603:13

Active Positive Energy

Received active energy in mWh

INT64

RO

 

F603:14

Active Negative Energy

Supplied active energy in mWh

INT64

RO

 

Index F604 PMX Total Active Fundamental

Index (hex)

Name

Meaning

Data type

Flags

Default

F604:0

PMX Total Active Fundamental

Max. subindex

UINT8

RO

0x14 (20dec)

F604:11

Active Power Fund

Active power of the fundamental oscillation in W

INT64

RO

 

F604:12

Active Energy Fund

Balanced active energy fundamental oscillation in mWh

INT64

RO

 

F604:13

Active Positive Energy Fund

Related active energy of the fundamental oscillation in mWh

INT64

RO

 

F604:14

Active Negative Energy Fund

Active energy fed into the system of the fundamental oscillation in mWh

INT64

RO

 

Index F605 PMX Total Apparent

Index (hex)

Name

Meaning

Data type

Flags

Default

F605:0

PMX Total Apparent

Max. subindex

UINT8

RO

0x14 (20dec)

F605:11

Apparent Power

Balanced apparent power in VA

INT64

RO

 

F605:12

Apparent Energy

Recorded apparent energy in mWh

INT64

RO

 

F605:13

Apparent Positive Energy

Received apparent energy in mWh

UINT64

RO

 

F605:14

Apparent Negative Energy

Supplied apparent energy in mWh

UINT64

RO

 

Index F606 PMX Total Apparent Fundamental

Index (hex)

Name

Meaning

Data type

Flags

Default

F606:0

PMX Total Apparent Fundamental

Max. subindex

UINT8

RO

0x14 (20dec)

F606:11

Apparent Power Fund

Apparent power fundamental in VA

INT64

RO

 

F606:12

Apparent Energy

Recorded apparent energy in mWh

INT64

RO

 

F606:13

Apparent Positive Energy

Received apparent energy in mWh

UINT64

RO

 

F606:14

Apparent Negative Energy

Supplied apparent energy in mWh

UINT64

RO

 

Index F607 PMX Total Reactive

Index (hex)

Name

Meaning

Data type

Flags

Default

F607:0

PMX Total Reactive

Max. subindex

UINT8

RO

0x14 (20dec)

F607:11

Reactive Power

Balanced reactive power in Var

INT64

RO

 

F607:12

Reactive Energy

Recorded reactive energy in mWh

INT64

RO

 

F607:13

Reactive Positive Energy

Received reactive energy in mWh

UINT64

RO

 

F607:14

Reactive Negative Energy

Supplied reactive energy in mWh

UINT64

RO

 

Index F608 PMX Total Reactive Fundamental

Index (hex)

Name

Meaning

Data type

Flags

Default

F608:0

PMX Total Reactive Fundamental

Max. subindex

UINT8

RO

0x14 (20dec)

F608:11

Reactive Power Fund

Balanced reactive power of the fundamental oscillation in Var

INT64

RO

 

F608:12

Reactive Energy

Recorded reactive energy in mWh

INT64

RO

 

F608:13

Reactive Positive Energy

Received reactive energy in mWh

UINT64

RO

 

F608:14

Reactive Negative Energy

Supplied reactive energy in mWh

UINT64

RO

 

Index F609 PMX Total L-L Voltages

Index (hex)

Name

Meaning

Data type

Flags

Default

F609:0

PMX Total L-L Voltages

Max. subindex

UINT8

RO

0x13 (19dec)

F609:11

L1-L2 Voltage

RMS value of the phase-to-phase voltage between L1 and L2 in V

REAL32

RO

0.000000 (0.000000e+000)

F609:12

L2-L3 Voltage

RMS value of the phase-to-phase voltage between L2 and L3 in V

REAL32

RO

0.000000 (0.000000e+000)

F609:13

L3-L1 Voltage

RMS value of the phase-to-phase voltage between L3 and L1 in V

REAL32

RO

0.000000 (0.000000e+000)

Index F60A PMX Variant Value In

Index (hex)

Name

Meaning

Data type

Flags

Default

F60A:0

PMX Variant Value In

Max. subindex

UINT8

RO

0x18 (24dec)

F60A:10

TxPDO Toggle

The TxPDO toggle is toggled by the slave when the data of the associated TxPDO is updated.

BOOLEAN

RO

0x00 (0dec)

F60A:11

Index 1 REAL

Acknowledge for variable output value 1

UINT16

RO

0x0000 (0dec)

F60A:12

Value 1 REAL

variable output value channel 1

REAL32

RO

0.000000 (0.000000e+000)

F60A:13

Index 2 REAL

Acknowledge for variable output value 2

UINT16

RO

0x0000 (0dec)

F60A:14

Value 2 REAL

variable output value channel 2

REAL32

RO

0.000000 (0.000000e+000)

F60A:15

Index 3 REAL

Acknowledge for variable output value 3

UINT16

RO

0x0000 (0dec)

F60A:16

Value 3 REAL

variable output value channel 3

REAL32

RO

0.000000 (0.000000e+000)

F60A:17

Index 4 ULINT

Acknowledge for variable output value 4

UINT16

RO

0x0000 (0dec)

F60A:18

Value 4 ULINT

variable output value channel 4

UINT64

RO

 

Index F60B PMX Total Statistic Power

Index (hex)

Name

Meaning

Data type

Flags

Default

F60B:0

PMX Total Statistic Power

Max. subindex

UINT8

RO

0x19 (25dec)

F60B:11

Active Power Avg

Average total active power of the last interval in W

REAL32

RO

0.000000 (0.000000e+000)

F60B:12

Active Power Min

Minimum total active power in the last interval in W

REAL32

RO

0.000000 (0.000000e+000)

F60B:13

Active Power Max

Maximum total active power in the last interval in W

REAL32

RO

0.000000 (0.000000e+000)

F60B:14

Apparent Power Avg

Average total apparent power of the last interval in VA

REAL32

RO

0.000000 (0.000000e+000)

F60B:15

Apparent Power Min

Minimum total apparent power in the last interval in VA

REAL32

RO

0.000000 (0.000000e+000)

F60B:16

Apparent Power Max

Maximum total apparent power in the last interval in VA

REAL32

RO

0.000000 (0.000000e+000)

F60B:17

Reactive Power Avg

Average total reactive power average in the last interval in var

REAL32

RO

0.000000 (0.000000e+000)

F60B:18

Reactive Power Min

Minimum total reactive power in the last interval in var

REAL32

RO

0.000000 (0.000000e+000)

F60B:19

Reactive Power Max

Maximum total reactive power in the last interval in var

REAL32

RO

0.000000 (0.000000e+000)

Index F60C PMX Total Statistic PQF

Index (hex)

Name

Meaning

Data type

Flags

Default

F60C:0

PMX Total Statistic PQF

Max. subindex

UINT8

RO

0x13 (19dec)

F60C:11

PQF Avg

Average value of the power quality factor in the last interval

REAL32

RO

0.000000 (0.000000e+000)

F60C:12

PQF Min

Minimum power quality factor in the last interval

REAL32

RO

0.000000 (0.000000e+000)

F60C:13

PQF Max

Maximum power quality factor in the last interval

REAL32

RO

0.000000 (0.000000e+000)

Index F60D PMX Total Interval Energy

Index (hex)

Name

Meaning

Data type

Flags

Default

F60D:0

PMX Total Interval Energy

Max. subindex

UINT8

RO

0x19 (25dec)

F60D:10

TxPDO Toggle

The TxPDO toggle is toggled by the slave when the data of the associated TxPDO is updated.

BOOLEAN

RO

0x00 (0dec)

F60D:11

Active Energy

Recorded total active energy in the last interval in mWh

REAL32

RO

0.000000 (0.000000e+000)

F60D:12

Active Energy Positive

Received total active energy in the last interval in mWh

REAL32

RO

0.000000 (0.000000e+000)

F60D:13

Active Energy Negative

Supplied total active energy in the last interval in mWh

REAL32

RO

0.000000 (0.000000e+000)

F60D:14

Apparent Energy

Recorded total apparent energy in the last interval in mWh

REAL32

RO

0.000000 (0.000000e+000)

F60D:15

Apparent Energy Positive

Received total apparent energy in the last interval in mWh

REAL32

RO

0.000000 (0.000000e+000)

F60D:16

Apparent Energy Negative

Supplied total apparent energy in the last interval in mWh

REAL32

RO

0.000000 (0.000000e+000)

F60D:17

Reactive Energy

Recorded total reactive energy in the last interval in mWh

REAL32

RO

0.000000 (0.000000e+000)

F60D:18

Reactive Energy Positive

Received total reactive energy in the last interval in mWh

REAL32

RO

0.000000 (0.000000e+000)

F60D:19

Reactive Energy Negative

Supplied total reactive energy in the last interval in mWh

REAL32

RO

0.000000 (0.000000e+000)

Index F60E PMX Total Interval Energy Fundamental

Index (hex)

Name

Meaning

Data type

Flags

Default

F60E:0

PMX Total Interval Energy Fundamental

Max. subindex

UINT8

RO

0x19 (25dec)

F60E:10

TxPDO Toggle

The TxPDO toggle is toggled by the slave when the data of the associated TxPDO is updated.

BOOLEAN

RO

0x00 (0dec)

F60E:11

Active Energy Fund

Recorded total active energy fundamental in the last interval in Wh

REAL32

RO

0.000000 (0.000000e+000)

F60E:12

Active Energy Positive Fund

Received total active energy fundamental in the last interval in Wh

REAL32

RO

0.000000 (0.000000e+000)

F60E:13

Active Energy Negative Fund

Supplied total active energy fundamental in the last interval in Wh

REAL32

RO

0.000000 (0.000000e+000)

F60E:14

Apparent Energy Fund

Recorded total apparent energy fundamental in the last interval in Wh

REAL32

RO

0.000000 (0.000000e+000)

F60E:15

Apparent Energy Positive Fund

Received total apparent energy fundamental in the last interval in Wh

REAL32

RO

0.000000 (0.000000e+000)

F60E:16

Apparent Energy Negative Fund

Supplied total apparent energy fundamental in the last interval in Wh

REAL32

RO

0.000000 (0.000000e+000)

F60E:17

Reactive Energy Fund

Recorded total reactive energy fundamental in the last interval in Wh

REAL32

RO

0.000000 (0.000000e+000)

F60E:18

Reactive Energy Positive Fund

Received total reactive energy fundamental in the last interval in Wh

REAL32

RO

0.000000 (0.000000e+000)

F60E:19

Reactive Energy Negative Fund

Supplied total reactive energy fundamental in the last interval in Wh

REAL32

RO

0.000000 (0.000000e+000)

Index F60F PMX Total System Angles

Index (hex)

Name

Meaning

Data type

Flags

Default

F60F:0

PMX Total System Angles

Max. subindex

UINT8

RO

0x15 (21dec)

F60F:11

Voltage Angle L1 L2

Angle between the phase voltages of L1 and L2

REAL32

RO

0.000000 (0.000000e+000)

F60F:12

Voltage Angle L1 L3

Angle between the phase voltages of L1 and L3

REAL32

RO

0.000000 (0.000000e+000)

F60F:13

Current Angle L1

Phase angle of the current from L1

REAL32

RO

0.000000 (0.000000e+000)

F60F:14

Current Angle L2

Phase angle of the current from L2

REAL32

RO

0.000000 (0.000000e+000)

F60F:15

Current Angle L3

Phase angle of the current from L3

REAL32

RO

0.000000 (0.000000e+000)

Index F610 PMX Total System

Index (hex)

Name

Meaning

Data type

Flags

Default

F610:0

PMX Total System

Max. subindex

UINT8

RO

0x13 (19dec)

F610:11

Positive Sequence

Voltage of the positive-sequence system

REAL32

RO

0.000000 (0.000000e+000)

F610:12

Negative Sequence

Voltage of the negative-sequence system

REAL32

RO

0.000000 (0.000000e+000)

F610:13

Zero Sequence

Voltage of the zero sequence system

REAL32

RO

0.000000 (0.000000e+000)

Index F611 PMX Total Statistic Power Fundamental

Index (hex)

Name

Meaning

Data type

Flags

Default

F611:0

PMX Total Statistic Power Fundamental

Max. subindex

UINT8

RO

0x18 (24dec)

F611:10

Active Power Avg Fund

Average total active power fundamental in the last interval in W

REAL32

RO

0.000000 (0.000000e+000)

F611:11

Active Power Min Fund

Minimum total active power fundamental in the last interval in W

REAL32

RO

0.000000 (0.000000e+000)

F611:12

Active Power Max Fund

Maximum total active power fundamental in the last interval in W

REAL32

RO

0.000000 (0.000000e+000)

F611:13

Apparent Power Avg Fund

Average total apparent power fundamental in the last interval in VA

REAL32

RO

0.000000 (0.000000e+000)

F611:14

Apparent Power Min Fund

Minimum total apparent power fundamental in the last interval in VA

REAL32

RO

0.000000 (0.000000e+000)

F611:15

Apparent Power Max Fund

Maximum total apparent power fundamental in the last interval in VA

REAL32

RO

0.000000 (0.000000e+000)

F611:16

Reactive Power Avg Fund

Average total reactive power fundamental in the last interval in var

REAL32

RO

0.000000 (0.000000e+000)

F611:17

Reactive Power Min Fund

Minimum total reactive power fundamental in the last interval in var

REAL32

RO

0.000000 (0.000000e+000)

F611:18

Reactive Power Max Fund

Maximum total reactive power fundamental in the last interval in var

REAL32

RO

0.000000 (0.000000e+000)

Index F612 PMX Total Active Reduced

Index (hex)

Name

Meaning

Data type

Flags

Default

F612:0

PMX Total Active Reduced

Max. subindex

UINT8

RO

0x12 (18dec)

F612:11

Active Power

Active power in W

REAL32

RO

0.000000 (0.000000e+000)

F612:12

Active Energy

Active energy in mWh

INT64

RO

0x00000000 (0dec)

Index F613 PMX Total Apparent Reduced

Index (hex)

Name

Meaning

Data type

Flags

Default

F613:0

PMX Total Apparent Reduced

Max. subindex

UINT8

RO

0x12 (18dec)

F613:11

Apparent Power

Apparent power in VA

REAL32

RO

0.000000 (0.000000e+000)

F613:12

Apparent Energy

Apparent energy in mVAh

INT64

RO

0x00000000 (0dec)

Index F614 PMX Total Reactive Reduced

Index (hex)

Name

Meaning

Data type

Flags

Default

F614:0

PMX Total Reactive Reduced

Max. subindex

UINT8

RO

0x12 (18dec)

F614:11

Reactive Power

Reactive power in var

REAL32

RO

0.000000 (0.000000e+000)

F614:12

Reactive Energy

Reactive energy in mvarh

INT64

RO

0x00000000 (0dec)

Index F615 PMX Total Interval Energy Reduced

Index (hex)

Name

Meaning

Data type

Flags

Default

F615:0

PMX Total Interval Energy Reduced

Max. subindex

UINT8

RO

0x13 (19dec)

F615:10

TxPDO Toggle

The TxPDO toggle is toggled by the slave when the data of the associated TxPDO is updated.

BOOLEAN

RO

0x00 (0dec)

F615:11

Active Energy

Recorded total active energy in the last interval in mWh

REAL32

RO

0.000000 (0.000000e+000)

F615:12

Apparent Energy

Recorded total apparent energy in the last interval in mVAh

REAL32

RO

0.000000 (0.000000e+000)

F615:13

Reactive Energy

Recorded total reactive energy in the last interval in mvarh

REAL32

RO

0.000000 (0.000000e+000)

Index F630 DPM Data

Index (hex)

Name

Meaning

Data type

Flags

Default

F630:0

DPM Data

Max. subindex

UINT8

RO

0x14 (20dec)

F630:01

SubIndex 001

 

UINT32

RO

0x00000000 (0dec)

F630:02

SubIndex 002

 

UINT32

RO

0x00000000 (0dec)

F630:03

SubIndex 003

 

UINT32

RO

0x00000000 (0dec)

F630:04

SubIndex 004

 

UINT32

RO

0x00000000 (0dec)

F630:05

SubIndex 005

 

UINT32

RO

0x00000000 (0dec)

F630:06

SubIndex 006

 

UINT32

RO

0x00000000 (0dec)

F630:07

SubIndex 007

 

UINT32

RO

0x00000000 (0dec)

F630:08

SubIndex 008

 

UINT32

RO

0x00000000 (0dec)

F630:09

SubIndex 009

 

UINT32

RO

0x00000000 (0dec)

F630:0A

SubIndex 010

 

UINT32

RO

0x00000000 (0dec)

F630:0B

SubIndex 011

 

UINT32

RO

0x00000000 (0dec)

F630:0C

SubIndex 012

 

UINT32

RO

0x00000000 (0dec)

F630:0D

SubIndex 013

 

UINT32

RO

0x00000000 (0dec)

F630:0E

SubIndex 014

 

UINT32

RO

0x00000000 (0dec)

F630:0F

SubIndex 015

 

UINT32

RO

0x00000000 (0dec)

F630:10

SubIndex 016

 

UINT32

RO

0x00000000 (0dec)

F630:11

SubIndex 017

 

UINT32

RO

0x00000000 (0dec)

F630:12

SubIndex 018

 

UINT32

RO

0x00000000 (0dec)

F630:13

SubIndex 019

 

UINT32

RO

0x00000000 (0dec)

F630:14

SubIndex 020

 

UINT32

RO

0x00000000 (0dec)