Power measurement on motor with 2 or 3 current transformers

WARNING

WARNING: Risk of electric shock!

If you do not connect terminal point N with the neutral conductor of your mains supply, you have to earth terminal point N, in order to avoid dangerous overvoltages in the event of a fault with a current transformer!

Notice

Attention! Risk of device damage!

Avoid confusing the current and voltage circuit during connection, since the direct connection of mains voltage to the terminal points for the current transformers (typical input resistance 220 mΩ) would destroy the power measurement terminal!

EL3443

Power measurement on motor with 2 or 3 current transformers 1:Fig.176: EL3443, Power measurement with 2 current transformers on a motor

In the circuit shown above (Fig. EL3443, power measurement with 2 current transformers on a motor), ensure that the three-phase system is either earth-free or has an earthed star point. Alternatively a transformer can be included in a Yy0 circuit.

EL3453

Power measurement on motor with 2 or 3 current transformers 2:Fig.177: EL3453, Power measurement with 3 current transformers on a motor

In the circuit shown above (Fig. EL3453, Power measurement with 3 current transformers on a motor), ensure that the three-phase system is either earth-free or has an earthed star point. Alternatively a transformer can be included in a Yy0 circuit.