Input data

Index 60n0 PMX status (n = 0, 1, 2)

Index (hex)

Name

Meaning

Data type

Flags

Default

60n0:0

PMX Status

Max. subindex

UINT8

RO

0x10 (16dec)

60n0:01

Voltage Sign Bit

Indicates the sign of the current sine wave voltage:

1 = U > 0V
0 = U < 0V

BOOLEAN

RO

0x00 (0dec)

60n0:02

Overvoltage

Maximum measurable voltage is exceeded.

BOOLEAN

RO

0x00 (0dec)

60n0:03

Overcurrent

Maximum measurable current is exceeded.

BOOLEAN

RO

0x00 (0dec)

60n0:04

Inaccurate Voltage

The measured voltage value is smaller than the value entered in CoE object "F800:15 Inaccurate Threshold Voltage".

BOOLEAN

RO

0x00 (0dec)

60n0:05

Inaccurate Current

The measured current value is smaller than the value entered in CoE object "F800:16 Inaccurate Threshold Current".

BOOLEAN

RO

0x00 (0dec)

60n0:06

Voltage Guard Warning

A warning limit of the voltage monitor has been breached.

BOOLEAN

RO

0x00 (0dec)

60n0:07

Voltage Guard Error

An error limit of the voltage monitor has been breached.

BOOLEAN

RO

0x00 (0dec)

6000:10

TxPDO Toggle

The TxPDO toggle is toggled by the slave when the data of the associated TxPDO is updated.

BOOLEAN

RO

0x00 (0dec)

Index 60n1 PMX Basic (n = 0, 1, 2)

Index (hex)

Name

Meaning

Data type

Flags

Default

60n1:0

PMX Basic

 Max. subindex

UINT8

RO

0x12 (18dec)

60n1:11

Voltage

 RMS value of the voltage in V

REAL32

RO

0.000000 (0.000000e+000)

60n1:12

Current

 RMS value of the current in A

REAL32

RO

0.000000 (0.000000e+000)

Index 60n2 PMX Power (n = 0, 1, 2)

Index (hex)

Name

Meaning

Data type

Flags

Default

60n2:0

PMX Power

 Max. subindex

UINT8

RO

0x14 (20dec)

60n2:11

Active Power

 Active power in W

REAL32

RO

0.000000 (0.000000e+000)

60n2:12

Apparent Power

 Apparent power in VA

REAL32

RO

0.000000 (0.000000e+000)

60n2:13

Reactive Power

 Reactive power in var

REAL32

RO

0.000000 (0.000000e+000)

60n2:14

Power Factor

 Power factor

REAL32

RO

0.000000 (0.000000e+000)

Index 60n4 PMX Energy (n = 0, 1, 2)

Index (hex)

Name

Meaning

Data type

Flags

Default

60n4:0

PMX Energy

Max. subindex

UINT8

RO

0x13 (19dec)

60n4:11

Active Energy

Active energy in mWh

INT64

RO

 

60n4:12

Apparent Energy

Apparent energy in mVAh

INT64

RO

 

60n4:13

Reactive Energy

Reactive energy in mvarh

INT64

RO

 

Index 60n6 PMX Timing (n = 0, 1, 2)

Index (hex)

Name

Meaning

Data type

Flags

Default

60n6:0

PMX Timing

Max Subindex

UINT8

RO

0x12 (18dec)

60n6:12

Voltage Last Zero Crossing

Last detected voltage zero crossing as distributed clock time

UINT64

RO

 

Index 60n7 PMX Advanced (n = 0, 1, 2)

Index (hex)

Name

Meaning

Data type

Flags

Default

60n7:0

PMX Advanced

Max. subindex

UINT8

RO

0x14 (20dec)

60n7:10

TxPDO Toggle

The TxPDO toggle is toggled by the slave when the data of the associated TxPDO is updated.

BOOLEAN

RO

0x00 (0dec)

60n7:11

Voltage Total Harmonic Distortion

"Total Harmonic Distortion" is the distortion factor of the voltage. It indicates the ratio of the harmonic components of an oscillation relative to its fundamental in %.

REAL32

RO

0.000000 (0.000000e+000)

60n7:12

Current Distortion Factor

The "Current Distortion Factor" is also referred to as TDD (Total Demand Distortion). It indicates the ratio between the current harmonics and the maximum current (EL3443: 1 A and EL3443-0010: 5 A, EL3453: 100 mA/1 A/5 A). Specified in % of the maximum current.

REAL32

RO

0.000000 (0.000000e+000)

60n7:13

Current Total Harmonic Distortion

"Total Harmonic Distortion" is the distortion factor of the current. It indicates the ratio of the harmonic components of an oscillation relative to its fundamental in %.

REAL32

RO

0.000000 (0.000000e+000)

60n7:14

Cos phi

Phase angle of the fundamental wave in degrees

REAL32

RO

0.000000 (0.000000e+000)

Index 60n8 PMX Statistic Voltage (n = 0, 1, 2)

Index (hex)

Name

Meaning

Data type

Flags

Default

60n8:0

PMX Statistic Voltage

Max. subindex

UINT8

RO

0x13 (19dec)

60n8:11

Voltage Peak

Peak value of the instantaneous voltage in the last interval in V

REAL32

RO

0.000000 (0.000000e+000)

60n8:12

Voltage RMS Minimum

Minimum RMS value of the voltage in the last interval in V

REAL32

RO

0.000000 (0.000000e+000)

60n8:13

Voltage RMS Maximum

Maximum RMS value of the voltage in the last interval in V

REAL32

RO

0.000000 (0.000000e+000)

Index 60n9 PMX Statistic Current (n = 0, 1, 2)

Index (hex)

Name

Meaning

Data type

Flags

Default

60n9:0

PMX Statistic Current

Max. subindex

UINT8

RO

0x13 (19dec)

60n9:11

Current Peak

Peak value of the instantaneous current in the last interval in A

REAL32

RO

0.000000 (0.000000e+000)

60n9:12

Current RMS Minimum

Minimum RMS value of the current in the last interval in A

REAL32

RO

0.000000 (0.000000e+000)

60n9:13

Current RMS Maximum

Maximum RMS value of the current in the last interval in A

REAL32

RO

0.000000 (0.000000e+000)

Index 60nA PMX Statistic Power (n = 0, 1, 2)

Index (hex)

Name

Meaning

Data type

Flags

Default

60nA:0

PMX Statistic Power

Max. subindex

UINT8

RO

0x19 (25dec)

60nA:11

Active Power Avg

Average active power in the last interval in W

REAL32

RO

0.000000 (0.000000e+000)

60nA:12

Active Power Min

Minimum active power in the last interval in W

REAL32

RO

0.000000 (0.000000e+000)

60nA:13

Active Power Max

Maximum active power in the last interval in W

REAL32

RO

0.000000 (0.000000e+000)

60nA:14

Apparent Power Avg

Average apparent power in the last interval in VA

REAL32

RO

0.000000 (0.000000e+000)

60nA:15

Apparent Power Max

Maximum apparent power in the last interval in VA

REAL32

RO

0.000000 (0.000000e+000)

60nA:16

Reactive Power Avg

Average reactive power average in the last interval in var

REAL32

RO

0.000000 (0.000000e+000)

60nA:17

Reactive Power Min

Minimum reactive power in the last interval in var

REAL32

RO

0.000000 (0.000000e+000)

60nA:18

Reactive Power Max

Maximum reactive power in the last interval in var

REAL32

RO

0.000000 (0.000000e+000)

60nA:19

Apparent Power Min

Minimum apparent power in the last interval in VA

REAL32

RO

0.000000 (0.000000e+000)

Index 60nB PMX Classic (n = 0, 1, 2)

Index (hex)

Name

Meaning

Data type

Flags

Default

600B:0

PMX Classic

Max. subindex

UINT8

RO

0x16 (22dec)

600B:10

TxPDO Toggle

The TxPDO toggle is toggled by the slave when the data of the associated TxPDO is updated.

BOOLEAN

RO

0x00 (0dec)

600B:11

Voltage

RMS value of the voltage in 0.001 V

INT32

RO

0x00000000 (0dec)

600B:12

Current

RMS value of the current in 0.0001 A

INT32

RO

0x00000000 (0dec)

600B:13

Frequency

Frequency of the fundamental in 0.001 Hz

INT32

RO

0x00000000 (0dec)

600B:14

Active Power

Active power in 0.001 W

INT32

RO

0x00000000 (0dec)

600B:15

Apparent Power

Apparent power in 0.001 VA

INT32

RO

0x00000000 (0dec)

600B:16

Reactive Power

Reactive power in 0.001 var

INT32

RO

0x00000000 (0dec)

Index F600 PMX Total Status

Index (hex)

Name

Meaning

Data type

Flags

Default

F600:0

PMX Total Status

Max. subindex

UINT8

RO

0x11 (17dec)

F600:01

System State

Overall system state (as a logical disjunction of voltage guard errors, phase sequence, overvoltage, overcurrent and frequency guard errors)

BOOLEAN

RO

0x00 (0dec)

F600:02

Grid Direction

Phase sequence L1 - L2 - L3 correctly detected (with clockwise 3-phase mains)

BOOLEAN

RO

0x00 (0dec)

F600:03

Frequency Guard Warning

A warning limit of the frequency monitor has been breached.

BOOLEAN

RO

0x00 (0dec)

F600:04

Frequency Guard Error

An error limit of the frequency monitor has been breached.

BOOLEAN

RO

0x00 (0dec)

F600:05

Neutral Current Guard Warning

A warning limit of the neutral conductor current monitor has been breached.

BOOLEAN

RO

0x00 (0dec)

F600:06

Neutral Current Guard Error

An error limit of the neutral conductor current monitor has been breached.

BOOLEAN

RO

0x00 (0dec)

F600:07

Active Power Guard Warning

A warning limit of the active power monitor has been breached.

BOOLEAN

RO

0x00 (0dec)

F600:08

Active Power Guard Error

An error limit of the active power monitor has been breached.

BOOLEAN

RO

0x00 (0dec)

F600:09

Apparent Power Guard Warning

A warning limit of the apparent power monitor has been breached.

BOOLEAN

RO

0x00 (0dec)

F600:0A

Apparent Power Guard Error

An error limit of the apparent power monitor has been breached.

BOOLEAN

RO

0x00 (0dec)

F600:0B

Power Quality Guard Warning

A warning limit of the PQF monitor has been breached.

BOOLEAN

RO

0x00 (0dec)

F600:0C

Power Quality Guard Error

An error limit of the PQF monitor has been breached.

BOOLEAN

RO

0x00 (0dec)

F600:0F

TxPDO State

TRUE for general error

BOOLEAN

RO

0x00 (0dec)

F600:10

TxPDO Toggle

The TxPDO toggle is toggled by the slave when the data of the associated TxPDO is updated.

BOOLEAN

RO

0x00 (0dec)

F600:11

Power Quality Factor

Analog value of the voltage quality between 1.0 and 0 (see basic function principles - Power Quality Factor)

REAL32

RO

0.000000 (0.000000e+000)

Index F601 PMX Total Basic

Index (hex)

Name

Meaning

Data type

Flags

Default

F601:0

PMX Total Basic

Max. subindex

UINT8

RO

0x13 (19dec)

F601:11

Frequency

Frequency in Hz

REAL32

RO

0.000000 (0.000000e+000)

F601:12

Power Factor

Power factor

REAL32

RO

0.000000 (0.000000e+000)

F601:13

Calculated Neutral Line Current

Calculated RMS value of the neutral conductor current in A

REAL32

RO

0.000000 (0.000000e+000)

Index F602 PMX Total Advanced

Index (hex)

Name

Meaning

Data type

Flags

Default

F602:0

PMX Total Advanced

Max. subindex

UINT8

RO

0x14 (20dec)

F602:01

Unbalance Guard Warning

A warning limit of the unbalance monitor has been breached.

BOOLEAN

RO

0x00 (0dec)

F602:02

Unbalance Guard Error

An error limit of the unbalance monitor has been breached.

BOOLEAN

RO

0x00 (0dec)

F602:10

TxPDO Toggle

The TxPDO toggle is toggled by the slave when the data of the associated TxPDO is updated.

BOOLEAN

RO

0x00 (0dec)

F602:11

Max Voltage Harmonic Distortion

Maximum distortion factor of all three phase voltages in %

REAL32

RO

0.000000 (0.000000e+000)

F602:12

Max Current Harmonic Distortion

Maximum distortion factor of all three phase currents in %

REAL32

RO

0.000000 (0.000000e+000)

F602:13

Max Current Distortion Factor

Maximum "Total Demand Distortion" value of all three phases in %

REAL32

RO

0.000000 (0.000000e+000)

F602:14

Voltage Unbalance

Ratio between negative and positive voltage system in %

REAL32

RO

0.000000 (0.000000e+000)

Index F603 PMX Total Active

Index (hex)

Name

Meaning

Data type

Flags

Default

F603:0

PMX Total Active

Max. subindex

UINT8

RO

0x14 (20dec)

F603:11

Active Power

Active power in W

REAL32

RO

0.000000 (0.000000e+000)

F603:12

Active Energy

Recorded active energy in mWh

INT64

RO

 

F603:13

Active Positive Energy

Received active energy in mWh

INT64

RO

 

F603:14

Active Negative Energy

Supplied active energy in mWh

INT64

RO

 

Index F605 PMX Total Apparent

Index (hex)

Name

Meaning

Data type

Flags

Default

F605:0

PMX Total Apparent

Max. subindex

UINT8

RO

0x14 (20dec)

F605:11

Apparent Power

Balanced apparent power in VA

INT64

RO

 

F605:12

Apparent Energy

Recorded apparent energy in mWh

INT64

RO

 

F605:13

Apparent Positive Energy

Received apparent energy in mWh

UINT64

RO

 

F605:14

Apparent Negative Energy

Supplied apparent energy in mWh

UINT64

RO

 

Index F607 PMX Total Reactive

Index (hex)

Name

Meaning

Data type

Flags

Default

F607:0

PMX Total Reactive

Max. subindex

UINT8

RO

0x14 (20dec)

F607:11

Reactive Power

Balanced reactive power in Var

INT64

RO

 

F607:12

Reactive Energy

Recorded reactive energy in mWh

INT64

RO

 

F607:13

Reactive Positive Energy

Received reactive energy in mWh

UINT64

RO

 

F607:14

Reactive Negative Energy

Supplied reactive energy in mWh

UINT64

RO

 

Index F609 PMX Total L-L Voltages

Index (hex)

Name

Meaning

Data type

Flags

Default

F609:0

PMX Total L-L Voltages

Max. subindex

UINT8

RO

0x13 (19dec)

F609:11

L1-L2 Voltage

RMS value of the phase-to-phase voltage between L1 and L2 in V

REAL32

RO

0.000000 (0.000000e+000)

F609:12

L2-L3 Voltage

RMS value of the phase-to-phase voltage between L2 and L3 in V

REAL32

RO

0.000000 (0.000000e+000)

F609:13

L3-L1 Voltage

RMS value of the phase-to-phase voltage between L3 and L1 in V

REAL32

RO

0.000000 (0.000000e+000)

Index F60A PMX Variant Value In

Index (hex)

Name

Meaning

Data type

Flags

Default

F60A:0

PMX Variant Value In

Max. subindex

UINT8

RO

0x18 (24dec)

F60A:10

TxPDO Toggle

The TxPDO toggle is toggled by the slave when the data of the associated TxPDO is updated.

BOOLEAN

RO

0x00 (0dec)

F60A:11

Index 1 REAL

Acknowledge for variable output value 1

UINT16

RO

0x0000 (0dec)

F60A:12

Value 1 REAL

variable output value channel 1

REAL32

RO

0.000000 (0.000000e+000)

F60A:13

Index 2 REAL

Acknowledge for variable output value 2

UINT16

RO

0x0000 (0dec)

F60A:14

Value 2 REAL

variable output value channel 2

REAL32

RO

0.000000 (0.000000e+000)

F60A:15

Index 3 REAL

Acknowledge for variable output value 3

UINT16

RO

0x0000 (0dec)

F60A:16

Value 3 REAL

variable output value channel 3

REAL32

RO

0.000000 (0.000000e+000)

F60A:17

Index 4 ULINT

Acknowledge for variable output value 4

UINT16

RO

0x0000 (0dec)

F60A:18

Value 4 ULINT

variable output value channel 4

UINT64

RO

 

Index F60B PMX Total Statistic Power

Index (hex)

Name

Meaning

Data type

Flags

Default

F60B:0

PMX Total Statistic Power

Max. subindex

UINT8

RO

0x19 (25dec)

F60B:11

Active Power Avg

Average total active power of the last interval in W

REAL32

RO

0.000000 (0.000000e+000)

F60B:12

Active Power Min

Minimum total active power in the last interval in W

REAL32

RO

0.000000 (0.000000e+000)

F60B:13

Active Power Max

Maximum total active power in the last interval in W

REAL32

RO

0.000000 (0.000000e+000)

F60B:14

Apparent Power Avg

Average total apparent power of the last interval in VA

REAL32

RO

0.000000 (0.000000e+000)

F60B:15

Apparent Power Min

Minimum total apparent power in the last interval in VA

REAL32

RO

0.000000 (0.000000e+000)

F60B:16

Apparent Power Max

Maximum total apparent power in the last interval in VA

REAL32

RO

0.000000 (0.000000e+000)

F60B:17

Reactive Power Avg

Average total reactive power average in the last interval in var

REAL32

RO

0.000000 (0.000000e+000)

F60B:18

Reactive Power Min

Minimum total reactive power in the last interval in var

REAL32

RO

0.000000 (0.000000e+000)

F60B:19

Reactive Power Max

Maximum total reactive power in the last interval in var

REAL32

RO

0.000000 (0.000000e+000)

Index F60C PMX Total Statistic PQF

Index (hex)

Name

Meaning

Data type

Flags

Default

F60C:0

PMX Total Statistic PQF

Max. subindex

UINT8

RO

0x13 (19dec)

F60C:11

PQF Avg

Average value of the power quality factor in the last interval

REAL32

RO

0.000000 (0.000000e+000)

F60C:12

PQF Min

Minimum power quality factor in the last interval

REAL32

RO

0.000000 (0.000000e+000)

F60C:13

PQF Max

Maximum power quality factor in the last interval

REAL32

RO

0.000000 (0.000000e+000)

Index F60D PMX Total Interval Energy

Index (hex)

Name

Meaning

Data type

Flags

Default

F60D:0

PMX Total Interval Energy

Max. subindex

UINT8

RO

0x19 (25dec)

F60D:10

TxPDO Toggle

The TxPDO toggle is toggled by the slave when the data of the associated TxPDO is updated.

BOOLEAN

RO

0x00 (0dec)

F60D:11

Active Energy

Recorded total active energy in the last interval in mWh

REAL32

RO

0.000000 (0.000000e+000)

F60D:12

Active Energy Positive

Received total active energy in the last interval in mWh

REAL32

RO

0.000000 (0.000000e+000)

F60D:13

Active Energy Negative

Supplied total active energy in the last interval in mWh

REAL32

RO

0.000000 (0.000000e+000)

F60D:14

Apparent Energy

Recorded total apparent energy in the last interval in mWh

REAL32

RO

0.000000 (0.000000e+000)

F60D:15

Apparent Energy Positive

Received total apparent energy in the last interval in mWh

REAL32

RO

0.000000 (0.000000e+000)

F60D:16

Apparent Energy Negative

Supplied total apparent energy in the last interval in mWh

REAL32

RO

0.000000 (0.000000e+000)

F60D:17

Reactive Energy

Recorded total reactive energy in the last interval in mWh

REAL32

RO

0.000000 (0.000000e+000)

F60D:18

Reactive Energy Positive

Received total reactive energy in the last interval in mWh

REAL32

RO

0.000000 (0.000000e+000)

F60D:19

Reactive Energy Negative

Supplied total reactive energy in the last interval in mWh

REAL32

RO

0.000000 (0.000000e+000)

Index F612 PMX Total Active Reduced

Index (hex)

Name

Meaning

Data type

Flags

Default

F612:0

PMX Total Active Reduced

Max. subindex

UINT8

RO

0x12 (18dec)

F612:11

Active Power

Active power in W

REAL32

RO

0.000000 (0.000000e+000)

F612:12

Active Energy

Active energy in mWh

INT64

RO

0x00000000 (0dec)

Index F613 PMX Total Apparent Reduced

Index (hex)

Name

Meaning

Data type

Flags

Default

F613:0

PMX Total Apparent Reduced

Max. subindex

UINT8

RO

0x12 (18dec)

F613:11

Apparent Power

Apparent power in VA

REAL32

RO

0.000000 (0.000000e+000)

F613:12

Apparent Energy

Apparent energy in mVAh

INT64

RO

0x00000000 (0dec)

Index F614 PMX Total Reactive Reduced

Index (hex)

Name

Meaning

Data type

Flags

Default

F614:0

PMX Total Reactive Reduced

Max. subindex

UINT8

RO

0x12 (18dec)

F614:11

Reactive Power

Reactive power in var

REAL32

RO

0.000000 (0.000000e+000)

F614:12

Reactive Energy

Reactive energy in mvarh

INT64

RO

0x00000000 (0dec)

Index F615 PMX Total Interval Energy Reduced

Index (hex)

Name

Meaning

Data type

Flags

Default

F615:0

PMX Total Interval Energy Reduced

Max. subindex

UINT8

RO

0x13 (19dec)

F615:10

TxPDO Toggle

The TxPDO toggle is toggled by the slave when the data of the associated TxPDO is updated.

BOOLEAN

RO

0x00 (0dec)

F615:11

Active Energy

Recorded total active energy in the last interval in mWh

REAL32

RO

0.000000 (0.000000e+000)

F615:12

Apparent Energy

Recorded total apparent energy in the last interval in mVAh

REAL32

RO

0.000000 (0.000000e+000)

F615:13

Reactive Energy

Recorded total reactive energy in the last interval in mvarh

REAL32

RO

0.000000 (0.000000e+000)

Index F630 DPM Data

Index (hex)

Name

Meaning

Data type

Flags

Default

F630:0

DPM Data

Max. subindex

UINT8

RO

0x14 (20dec)

F630:01

SubIndex 001

 

UINT32

RO

0x00000000 (0dec)

F630:02

SubIndex 002

 

UINT32

RO

0x00000000 (0dec)

F630:03

SubIndex 003

 

UINT32

RO

0x00000000 (0dec)

F630:04

SubIndex 004

 

UINT32

RO

0x00000000 (0dec)

F630:05

SubIndex 005

 

UINT32

RO

0x00000000 (0dec)

F630:06

SubIndex 006

 

UINT32

RO

0x00000000 (0dec)

F630:07

SubIndex 007

 

UINT32

RO

0x00000000 (0dec)

F630:08

SubIndex 008

 

UINT32

RO

0x00000000 (0dec)

F630:09

SubIndex 009

 

UINT32

RO

0x00000000 (0dec)

F630:0A

SubIndex 010

 

UINT32

RO

0x00000000 (0dec)

F630:0B

SubIndex 011

 

UINT32

RO

0x00000000 (0dec)

F630:0C

SubIndex 012

 

UINT32

RO

0x00000000 (0dec)

F630:0D

SubIndex 013

 

UINT32

RO

0x00000000 (0dec)

F630:0E

SubIndex 014

 

UINT32

RO

0x00000000 (0dec)

F630:0F

SubIndex 015

 

UINT32

RO

0x00000000 (0dec)

F630:10

SubIndex 016

 

UINT32

RO

0x00000000 (0dec)

F630:11

SubIndex 017

 

UINT32

RO

0x00000000 (0dec)

F630:12

SubIndex 018

 

UINT32

RO

0x00000000 (0dec)

F630:13

SubIndex 019

 

UINT32

RO

0x00000000 (0dec)

F630:14

SubIndex 020

 

UINT32

RO

0x00000000 (0dec)